Lucent Technologies Lineage
®
2000 ECS-6 Controller J85501D-1
4 - 12 Installation and Setup
Issue 6 August 1998
Wiring
Each circuit pack in the controller may require connection to
systems outside the power plant or to other parts of the power
system. The user must provide these connections.
Basic Controller
The installer wiring associated with the basic controller is
connected to four removable terminal blocks on the 113A2. The
types of signals on these terminal blocks fall into four categories:
• Alarm Outputs (BD, HV, ACF, LV, MJF, MNF, PMJs,
and PMNs)
• Alarm Inputs (RMJ, RMN, and OS)
• Control Inputs (TEQ, TEL, TF/ER, and TRs)
• Miscellaneous Outputs (ABS and DG)
Three of the four terminal blocks (TB102, TB103, and TB104)
are assigned to the various office alarm outputs from the
controller. Terminal block TB101 has the connection points for
the remaining three categories of office interfaces. The signal on
each terminal is indicated on the label inside the controller front
panel.
Table 4-G provides a list of Terminal Block Pin Assignments for
the 113A2.
Table 4-G: Terminal Block Pin Assignments
for the 113A2 Control Unit
Pin No.
Designation
Definition
TB101-1 DG
Discharge
Ground
TB101-2
TF/ER
Timer Float/Equalize Return
TB101-3 OS
Open
String
Alarm
TB101-4
RMJ
Ringer Major Alarm
TB101-5 RMN
Ringer
Minor
Alarm
TB101-6 TEQ
Timer
Equalize
TB101-7 TFL
Timer
Float
TB101-8 ABS
Alarm
Battery
Supply
TB101-9 TR1
Transfer Shutdown from
Engine
TB101-10
TR2
Transfer Shutdown from
Engine
TB101-11
TR3
Transfer Shutdown from
Engine
TB101-12
TR4
Transfer Shutdown from
Engine