![Lucent Technologies J85501D-1 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/lucent-technologies/j85501d-1/j85501d-1_product-manual_1946207039.webp)
Lucent Technologies Lineage
®
2000 ECS-6 Controller J85501D-1
Issue 6 August 1998
Installation and Setup 4 - 3
Table 4-A: Default Factory Settings for Non-X Controllers
Jumper Settings
Board
Header
Jumper Pins
Function
Backplane
846199602
P602.1
2 and 3
-48 Volts
P602.2
P602.3
P602.4
CP1
P105
1 and 2
Restart enabled
P106
1 and 2
Equalize disabled
P108
1 and 2
For SR-series rectifiers
CP4
(Display)
P401
1 and 2
Shunt size less than
1000A
CP3
P302
1 and 2
-48 Volts
Switch Settings (0 = Open, 1 = Closed)
Board
Switch
Function
Switch Setting
-1 -2 -3 -4 -5 -6 -7 -8
CP1
SW101
HV/EQ Level
(-57 Volts)
1 1 0 0 1 0 N/A
SW102
HV/FL Level
(-55 Volts)
1 1 0 0 1 0 N/A
SW103
BD Level
(-53 Volts)
1 0 0 0 1 0 N/A
SW109
Meter Shunt
(300 Amps)
1 0 0 0 1 1 N/A
CP2
SW202
(See Table 4-D)
0 1 0 1 0 0 0 0