7. Operation of the unit
7.1 Operation
The units are equipped with the CP1 control. This control controls the entire unit.
The control is extremely easy to adjust using the remote control or laptop / computer. If you choose to
operate via computer or laptop, no software is required. The software is completely web-based. So you can
connect the controller to your PC / laptop or network with a network cable and get full access via your web
browser.
There are two types of controllers to operate the unit.
The basic control is a compact, graphic, touch control panel for the everyday user of
central ventilation. The touch control panel is ideal for adjusting the comfort level where
ventilation is provided by a central ventilation unit. The color touchscreen is easy and
intuitive to use. Both the temperature and the air exchange can be adjusted. There is
also a timer setting to activate.
The advanced controller is a user-friendly control panel for installation within an air
handling unit or inside on the wall. The color touchscreen is easy and intuitive to
use. The menus are logical, easy to navigate and have easily recognizable symbols.
This controller is used for the commissioning and everyday operation of the air
handling unit and in connection with service. All system values can be seen while
the settings are password protected.
For detailed information about the controller, see
https://lucam-air.nl/handleiding/
7.2 Ease of use and safety
All menus and graphics are specially adapted to this specific version of the unit and the individual user and
contain only relevant data.
Operation may only be performed by authorized persons who have access to the system. Alarms of the unit
have the highest priority and are visualized by a red-light flashing. Both control units provide a full view in
terms of ease of use and safety and focuses on optimal reduced of energy consumption.
7.3 Manual
The operating manual for the respective control center is supplied separately.
7.4 Start-up of the unit
The controller is preprogrammed based on installed components and the basic setting.
The controller is programmed with the following boot order.
The unit is started by clock or manual operation in the following order
•
Return / outside air damper opens after delay (adjustable)
•
Bypass valve closes 100% (heat recovery)
•
Reheater opens 50% (% adjustable)
•
Return fan starts (delayed adjustable)
•
Supply fan starts (delayed adjustable)
Start-up mode is completed, and the unit is operating.