7
5.2 Duct connection
The outside air intake duct and the return duct must be between the roof and/or facade duct and the air
handling unit insulated vapor-tight. This to prevent condensation on the outside of the ducts.
The indoor supply system must be insulated if it is outside the isolated shell of the building.
Pay attention
It is important that the ducts are connected to the correct connections, outside air intake,
exhaust air, return air, supply air.
There are marking stickers at the connections for checking.
To avoid unnecessary noise from the unit, it is recommended to install mufflers in the exhaust
and supply duct.
5.3 Connecting cabinet parts
When coupling cabinet parts, they must be placed directly opposite each other and by means of the brackets
to be connected. See picture.
Pay attention
It is important to provide the coupling parts to 1 part with a draft belt. E.g. 15-20mm. This
clamps as soon as the cabinets are pulled together, this gives a leak-free solution.