4  Unpacking and lifting

Always follow guidelines and instructions as given in the air cooled liquid coolers product manual 

AHE00050. 

Before lifting the unit, check the weight stated on the name plate, located on the inlet connection 

side. Verify that the lifting equipment supports at least the unit weight plus 10%. 

•  Forklifts can be used only with 2 to 5 modules units.

•  When forklifts are used, forks must be longer than 2.5 m for safe lifting and be fully inserted 

under the unit. 

•  Unit shall be lifted only when empty.

Alfa-V VDD dry coolers can be delivered either on standard trucks or in containers. 

4.1  Unit delivered by standard truck

The procedure below applies to the unloading of units delivered on standard trucks.

2-5 fan pairs unit: 

can be unloaded from the side of the truck with 

the use of a forklift.  

6-9 fan pairs unit: 

shall be always lifted from above.

Follow the procedure described in paragraph 

"Lifting from above" for 6-8 modules unit.

9 fan pairs units are equipped by default with the 

container skid and should be unloaded follow-

ing the procedure described in paragraph "Unit 

delivered in a container" even if they are deliv-

ered by standard truck.

4.2  Unit delivered in a container

In case of container delivery, container skid option is to be selected in order to facilitate the loading 

and unloading operations. In case of 9 modules unit, skid is installed by default. Follow the proce-

dure below to unload the unit:

•  Remove any obstacle to allow the skid sliding out of the container.

•  Ensure the truck is stopped.

Содержание Alfa LU-VE Alfa-V VDD

Страница 1: ...ORIGINAL INSTRUCTIONS 30366474EN 03 Alfa V VDD Instruction manual Product description Product labels Transport lifting Installation Maintenance Spare parts...

Страница 2: ...ons 4 2 4 Code description 5 3 Product labels 5 4 Unpacking and lifting 4 1 Unit delivered by standard truck 8 4 2 Unit delivered in a container 8 4 3 Lifting from above 10 5 Installation 5 1 Containe...

Страница 3: ...tion until the conformity of the complete machine or cooling system has been declared according to the following standards and directives Pressure Equipment Directive 2014 68 EU Machine Directive 2006...

Страница 4: ...tection class IP54 according to DIN 40050 and integrated thermo contacts to provide reli able protection against thermal overload AC power supplies 400 50 3 400 60 3 and 460 60 3 EC power supply 380 4...

Страница 5: ...5 6 7 8 9 10 11 12 13 14 15 1 Alfa V dry cooler VDD standard Cu tube VDD6 5 8 Cu VDDY 5 8 SS304 2 Sound level fan code T turbo S standard L low Q quiet R residential E EC fan motor 3 Fan diameter 80 8...

Страница 6: ...g 5 Sn Motorfan data Vn 3 380 480V f 50 60Hz Country of origin Italy i E X A M P L E WARNING READ INSTRUCTION MANUAL BEFORE INSTALLATION AND MAINTENANCE TO AVOID INJURIES OR DAMAGE Manufacturer Manuf...

Страница 7: ...umber 8 Fan motor Fan motor item number 10 11 In Out Refrigerant connections inlet and outlet IN OUT Grounding Whenever electrical components supplied by Alfa LU VE have this sticker is mandatory to g...

Страница 8: ...or in containers 4 1 Unit delivered by standard truck The procedure below applies to the unloading of units delivered on standard trucks 2 5 fan pairs unit can be unloaded from the side of the truck w...

Страница 9: ...st 1 m The space between the unit and the roof of the container is reduced Contact with the roof can cause damage to the unit A B With a second forklift identified by letter B insert the forks under t...

Страница 10: ...g lugs to the crane hoisting beam following the procedure described in para graph Lifting from above When the crane holds up the unit remove forklift A Slightly lift the unit and slowly drive forward...

Страница 11: ...ademark registered and owned by LU VE Group Alfa LU VE reserves the right to change specifications without prior notification 2 MOD 4 FANS 3 MOD 6 FANS 4 MOD 8 FANS 5 MOD 10 FANS 6 MOD 12 FANS 7 MOD 1...

Страница 12: ...ption is selected in order to facilitate loading and unloading operations 5 fan pair units container skids have two additional feet which can be recognized because above them there is no coil support...

Страница 13: ...nd or to a beam structure and for the installation of vibration dampers 5 4 Concrete mounting base To avoid oxidation of the equipment feet it is strongly recommended to mount the heat exchanger on co...

Страница 14: ...must be carried out before positioning the unit Vibration dampers are to be positioned between the unit feet and the mounting base with the supplied M16 screw Fan pairs Vibration dampers 2 4 3 4 4 6...

Страница 15: ...icient space is available for maintenance Verify the structures supporting capacity regarding the weight of the unit s including the liquid Floor mounted Single unit Two or more units The unit spacing...

Страница 16: ...ds When walls with different configuration or heights than the ones shown in the previous pictures are present When more than 6 units are installed on a single platform When severe environmental loads...

Страница 17: ...nnections Switch on fan power supply Start the fans and verify fan direction After some operating time check the absence of air in the liquid circuit vent if needed and verify that current absorbtion...

Страница 18: ...osition Remount fasteners Use an anti corrosion coating like Geomet or comparable when remounting using new fixing bolts Restore the electric connections water trap as shown Check for correct fan dire...

Страница 19: ...LU VE reserves the right to change specifications without prior notification 8 Spare parts Spare parts for Alfa V VDD Fan Switch on off Switchboard Vibration damper Protection grids available on reque...

Страница 20: ...alfa luvegroup com...

Отзывы: