background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

BC216CE_DBL_LST_EN_0804.PDF • PAGE 4

A

Building Safety. Building Security.

Specifi cations

Mains voltage 

10/-15%, 50Hz

Connection power 

60VA

Output voltage 

typ. 28VDC

Output peak current 

max. 1.8A

Connection of external devices 

typ. 0.8A, site-specifi c

Own current consumption at 24V 

typ. 90mA (without optional componentries)

Ambient temperature 

-5°C to +50°C

Dimensions W × H × D 

478 × 266 (6 height units) × 95 (mm)

Colour 

gray-white, RAL 9002

Weight without accumulator 

approx. 6kg

Approvals (EN 54-2, EN 54-4) 

VdS G201017

 

FT 14/147/3/99 (Austria)

By installing a Network Interface Module NIF5-1M in the 

Fire Detection Control Panel BC216-1CE, the latter can 

be integrated as BCnet sectional control panel with dis-

play  and  operating  fi eld  into  a  Fire  Detection  Control 

Panel BCnet216. All sectional control panels are con-

nected  with  each  other  via  a  redundant  high-security 

network (the Global Security System network GSSnet).

Network Expansion of BC216-1CE

Permanent Connection

A variety of peripheral devices can be connected to the 

fi re detection control panel Series BC216-1CE and to 

the BCnet sectional control panel BC216-3CE:

• Fire brigade key safe

• Fire brigade control unit

• Acoustic and optical signaling devices

• External protocol printer

• Remote display and operating panels

• Remote indication unit

• Actuations

• Electronic monitoring system

•  Transmitting  device  for  the  actuation  of  pagers  via 

ESPA protocol

•  Modules  for  remote  parameterisation  and  remote 

maintenance via computer newtork, modem or GSM 

connection

•   Transmitter module for the transmission of messages 

via SMS or e-mail

 – and much more.

If  required,  the  BC216-1CE  or  the  BCnet216  can  be 

easily  expanded  to  an  extinguishing  control  panel  ac-

cording to EN 12094-1. The extinguishing control panel 

LC216-1 controls up to 8 fl ooding zones in one extin-

guishing  system,  without  hardware  redundancy.  The 

networked  extinguishing  control  panel  LCnet216  can 

control up to 127 fl ooding zones in a maximum of 127 

extinguishing systems.

The function of the extinguishing control panel is fully 

integrated into the fi re detection control panels Series 

BC216, a combined operation is therefore possible.

The LC216-1 and LCnet216 are certifi ed to EN 54-2, 

EN 54-4, EN 12094-1 and VdS as a pure extinguishing 

control panel and as a combined fi re detection and ex-

tinguishing control panel.

The  networked  extinguishing  control  panel  LCnet216 

can be optionally implemented with full hardware red-

undancy.

Extinguishing Control System

Содержание BCnet216: 19"

Страница 1: ...unctions and features correspond to the Fire Detection Control Panel BC216 1 to the full extent By installing a Network Interface Module NIF5 1M the BC216 1CE can be expanded to form a BCnet sectional control panel The BCnet Sectional Control Panel BC216 3CE is a mo dularly designed sectional control panel in 19 slide in technology without display and operating field Black Box control panel for the...

Страница 2: ...o logic sectors allows for the joint operation of defined parts of the system even beyond the limits of loops or sectional control panels The use of unshielded loop cables allows for cost saving and uncomplicated installation as well as for the possibility of reusing the existing cabling The LC text display BC216 1CE shows events with the full information such as floor room identification as well as ...

Страница 3: ...k members 9700 detector zones 9700 actuations 999 alarming devices 99 transmitting devices as well as 199 logic sectors Different interfaces are available for the con nection of external information devices e g a facility management system or a remote maintenance sys tem As you can see in the figure below cabling of the detec tors is required only between two neighboring sectional control panels Th...

Страница 4: ... BC216 1CE and to the BCnet sectional control panel BC216 3CE Fire brigade key safe Fire brigade control unit Acoustic and optical signaling devices External protocol printer Remote display and operating panels Remote indication unit Actuations Electronic monitoring system Transmitting device for the actuation of pagers via ESPA protocol Modules for remote parameterisation and remote maintenance v...

Страница 5: ...Order name Fire detection control panel BC216 1CE Control panel without display and operating unit Part No 214105 Order name BCnet sectional control panel n op BCnet216 3CE Network Interface Module for the integration of the BC216 1CE into the GSSnet Part No 214033 Order name Network Interface Module NIF5 1M Battery bracket Dimensions of the complete control panel with battery bracket 478 266 6 he...

Отзывы: