Chapter 14 Troubleshooting
14-
14
Error
code
Error cause
Action
(restart mode after taking an action)
Operation
status
LED
status
Diagnosis
point
detected by the
user program
Refer to flag to repeat the device and
then restart (according to parameter)
55
The number of
running standby
task exceeds the
designated range
If it occurs repeatedly after restart,
check the installation environment (if
error continues, request service
center)
Stop
(Run)
ERR: On
(P.S.: On)
While
running
the
program
60
E_STOP function
executed
After removing error causes which
starts E_STOP function in program,
power reinput
Stop
RUN: On
ERR: On
While
running
the
program
61
Operation error
STOP: after checking the detailed
information of operation error by
XG5000, modify the program.
RUN : refer to error step
Stop
(Run)
ERR: On
(P.S.: On)
While
running
the
program
500
Data memory backup
not possible
If not error in battery, power reinput
Remote mode is switched to STOP
mode.
Stop ERR:
On Reset
501
Time data error
If no error in battery, reset the time by
XG5000
- CHK:
On
Ordinary
time
502
Battery voltage falling Battery change in the state of power
input
- BAT:
On
Ordinary
time
Notes
1) If error codes 2 to 13 are displayed, check with your local service center.
2) Error code numbers greater than 22 can be checked with XG5000 Error History.