5. Function Code Table
5-18
CODE
NO.
Comm.
Addr.
CODE NAME
LCD DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT DEFAULT
EXT_18
7612 Option output 8
Output 8
5)
0000 ~ FFFF
HEX
0000
Yes
EXT_19
7613 Number of option input
Input Num
0 ~ 8
6)
-
2
Yes
EXT_20
7614 Option input 1
Input 1
6)
0000 ~ FFFF
HEX
0502
No
EXT_21
7615 Option input 2
Input 2
6)
0000 ~ FFFF
HEX
0500
No
EXT_22
7616 Option input 3
Input 3
6)
0000 ~ FFFF
HEX
0000
No
EXT_23
7617 Option input 4
Input 4
6)
0000 ~ FFFF
HEX
0000
No
EXT_24
7618 Option input 5
Input 5
6)
0000 ~ FFFF
HEX
0000
No
EXT_25
7619 Option input 6
Input 6
6)
0000 ~ FFFF
HEX
0000
No
EXT_26 761A Option input 7
Input 7
6)
0000 ~ FFFF
HEX
0000
No
EXT_27 761B Option input 8
Input 8
6)
0000 ~ FFFF
HEX
0000
No
EXT_30 761E 485 communication mode Parity/Stop
1)
0 (8None/1Stop)
1 (8None/2Stop)
2 (8Even/1Stop)
3 (8Odd/1Stop)
-
0
(8None/
1Stop)
Yes
EXT_31 761F
Delay time of 485
communication response
Delay Time
1)
2 ~ 1000
ms
5
Yes
EXT_32
7620
Station address for built-in
485
Int485 St ID
1 ~ 250
-
2
Yes
EXT_33
7621 Built-in 485 baudrate
Int485 Baud
0 (1200 bps)
1 (2400 bps)
2 (4800 bps)
3 (9600 bps)
4 (19200 bps)
5 (38400 bps)
-
3
(9600 bps)
Yes
EXT_34
7622
Built-in 485 communication
mode
Int485 Mode
0 (8None/1Stop)
1 (8None/2Stop)
2 (8Even/1Stop)
3 (8Odd/1Stop)
-
-
Yes
EXT_35
7623
Delay time for built-in 485
communication response
Int485 Delay
2 ~ 1000
-
0 (None)
Yes
EXT_36
7624
Run method when the
command of built-in 485 is
lost.
Int485 LostC
0 (None)
1 (FreeRun)
2 (Stop)
-
-
Yes
EXT_37
7625
Decision time for losing the
command of built-in 485
Int485 LostT
1.0 ~ 30.0
-
-
Yes
EXT_98
7662
Profibus data swap
Selection
SWAP Sel
0 (No) / 1 (Yes)
-
0 (No)
No
EXT_99
7663
Update for communication
parameter changes
Comm UpDate
4)
0 (No) / 1 (Yes)
-
0 (No)
No
1) It will be displayed when RS-485 communication option board is installed.
2) It will be displayed when PLC-GF communication option board is installed.
3) It will be displayed when DeviceNet communication option board is installed.
4) Itwill be displayed when Profibus communication option b oard is installed.
5) From EXT_11 to EXT_18 (Option ouput) are displayed according to the number from
EXT_11.
6) From EXT_20 to EXT_27 (Option input) are displayed according to the number from
EXT_19.
Refer to the appropriate option manual.