3. Installation and Wiring
3-11
Note 2) The power of 220VAC is must be supplied for the operation of internal
cooling fan and/or Magnetic contactor. Use insulated transformer to
separate from main power supply.
(30 ~ 160 kW: for the operation of FAN and MC, 220/500kW: for the
operation of FAN)
(Transformer capacity: above 30~75kW(100VA), 90~160kW(150VA),
220/500kW(500VA) recommended )
3.3 Power Circuit Terminal
3.3.1 Power circuit terminal arrangement
(1) AC power input type
CAUTION
Be sure that “N” is not Neutral Line but DCN(-) and P is DCP(+).
SV022, 037, 055, 075, 110, 150, 185, 220iV5-2(DB)
SV022, 037, 055, 075, 110, 150, 185, 220iV5-4(DB)
R
S
T
U
V
W
G
N(-)
B2
B1
P(+)
SV110, 150, 185, 220iV5-2(DB)(MD)
SV110, 150, 185, 220iV5-4(DB)(MD) *(MD) : Mold Type
R
S
T
U
V
W
N(-)
B2
B1
P(+)
SV300, 370iV5-2
SV300, 370, 450, 550, 750iV5-4
R
S
T
G
U
V
W
P1(+) P2(+) N(-)
G