Terminal Configuration
(S-EMPR MMP-PM)
Terminal Configuration
(S-EMPR MMP-CM)
Terminals
Description
Remarks
Va, Vb, Vc
Voltage input
Current model Blank
Z1, Z2
ZCT input
Universal (Z1, Z2 : 1.5mA)
Z2V, Z1V Dedicated (Z2V, Z1V : 100mV)
Z2V, Z1V
4~20mA (+), (-)
4~20mA output
-
TRX1+, TRX1-
RS485 communication
Modbus(1 channel)
TRX2+, TRX2-
A1, A2
Control power input
110Vac or 220Vac 50/60Hz
C1
Contact input Common
-
Lop/Stop, For,
Rev, Res, E/S
Contact input
RES : Reset, E/S: Emergency Stop
C2
Relay output Common
-
Main, Y, D, Auto,
Volt
Relay output
D: Delta, VOLT : output contacts
for voltage & power elements
C3
Relay output Common
Aux output Common
Aux
Relay output
Current element output contacts
Terminals
Description
Remarks
A1, A2
Operating power input terminal
110Vac or 220Vac 50/60Hz
C1
Contact point in put common
Lop/Stop, For, Rev, Res, E/S contact point
Lop/Stop
Lop operation mode selection and external stop S/W
-
For
External On(Forward) input S/W
On input in Lop/Auto operation
Rev
Reverse input S/W in forward/reverse starting
REV input in Lop/Auto operation
Res
External Reset S/W
Reset input in Lop operation
E/S
External Emergency Stop S/W
-
C2
Contact point output common
Main, Y, D, Auto contact point
Main
Motor On output
If forward/backward staring, forward rotation output
Y
Y-Delta starting: Y contact point output
-
Inverter starting: Inverter contact point output
-
Full voltage starting: No use
-
Forward/backward staring: No use
-
Reactor starting: No use
-
D
Y-Delta starting: Delta contact point output
-
Forward/backward staring: reverse rotation contact point output
-
Reactor starting: Reactor (R) contact point output
-
Inverter starting: Bypass contact point output
-
Full voltage starting: No use
-
Auto
Auto state signal output
If Auto state mode is selected
C3
Contact point output common
Aux contact point only
Aux
Current factors contact point output
-
Z1,Z2
Zero current transformer output connection terminal
Universal ZCT(200mA/1.5mA)
Z1V, Z2V
Zero current transformer output connection terminal
ZCT(200mA/100mV) for DMP
+,-
4~20mA output
-
TRX+,TRX-
RS485terminal
-
Voltage
Power
supply
Power
supply
Terminal Configuration / Wiring
&
cable connection
90
Electronic Motor Protection Relays
Содержание EMPR DMPi Series
Страница 2: ...Electronic Motor Protection Relays ...
Страница 34: ...DMPi Series LSIS Co Ltd 33 MEMO ...
Страница 60: ...GMP Series LSIS Co Ltd 59 MEMO ...
Страница 72: ...IMP Series MEMO LSIS Co Ltd 71 ...
Страница 98: ...MMP Series MEMO LSIS Co Ltd 97 ...
Страница 107: ...106 Electronic Motor Protection Relays MEMO ...