DMPi Series
LSIS Co.,Ltd.
15
Rated specifications / Model numbering system
Connection method
Penetrated / Terminal type
Protection functions
Overcurrent, phase fail, phase unbalance, stall, locked rotor,reverse phase,
ground fault (Type option)Instance (Type option)
Connection method
Penetrated / Terminaltype
Operating time characteristics
Thermal heat build-up inverse time / Non-thermal heat build-up inverse time / Definite time
Rated current
0.5~6A/5~65A(Rating option upon placing an order)
Display
4 digit, 7-Segment
Operating power
AC/DC 85~260V(50Hz/60Hz)
Reset method
Automatic
1~20min (only for overcurrent)
Manual
(Electrical reset)
Installation / Mounting method
Display can be installed separately, 35mm DIN rail / Screw installation
Tolerance
Current
±3%
Time
±5%
4~20mA output
±5%
Time setting
Startup delay
1~200sec
Operation delay
1~60sec
Aux. contact
Composition
3-SPST(Power supply 1a1b, i nstantaneous operation 1a)
Note1)
Capacity
3A/250VAC Resistive Load
Contact minimum load
100mA / 6VDC : (95-996, 97-98)
10mA / 5VDC ( 07-08)
ZCT Input
External
200mA/100mV(Exclusive ZCT)
Note2)
Built-in
Support (Separate connection unnecessary
Note2)
Service environment
Service temperature
-20℃ ~ 60℃
Storage temperature
-30℃ ~ 70℃
Relative humidity
Below 50% RH (Without condensation)
Insulation resistance
100MΩ/500VDC
Lightning impulse voltage
1.2X50us 5kV Prototype waveform supply
Fast transient
2kV/1Min
Power consumption
Below 2W
Rated specifications
Note 1. See No. 21 to 23 of A-Group in Setting menu If single phase is set, the device measures R/S/T phase. In HMI, the maximum phase of three phases is displayed without any indication of phase.
2. It is used when zero current detection type is selected.
3. This product is used to protect a low-voltage motor with 1000V or less
Model numbering system
Rated current
06i
0.5~6A
65i
5~65A
Connection method
S Terminal type
T Penetrated type
Additional function
-
Alarm
I + Instance
Ground fault
-
None
Z
External ZCT
B
Built-in ZCT
Communication
-
None
M RS485 MOD
A
4~20mA
Operating voltage
12 AC/DC85~260V
Auxiliary contact
2a1b
DMP
06i
Z
S
I
M
12
2a1b
Note) “-” models have
Alarm + Operating Time
+ Failure History storage
functions as the default.
“I” models have an
additional instance
protection function.
Содержание EMPR DMPi Series
Страница 2: ...Electronic Motor Protection Relays ...
Страница 34: ...DMPi Series LSIS Co Ltd 33 MEMO ...
Страница 60: ...GMP Series LSIS Co Ltd 59 MEMO ...
Страница 72: ...IMP Series MEMO LSIS Co Ltd 71 ...
Страница 98: ...MMP Series MEMO LSIS Co Ltd 97 ...
Страница 107: ...106 Electronic Motor Protection Relays MEMO ...