DMPi Series
LSIS Co.,Ltd.
23
Note 1) Upon initial setting, P-99 is displayed on the screen. Here, use the Up/Down key to change it into P-00 and press Enter. You are now ready for setting.
The DMPi main screen display (0.00A)
1. Press Enter from the main screen. (A-gr)
2. Press Enter from the A-gr screen. (1. PHR)
3. Press the Up-key menu 3 times from the 1.PHR screen. (4.d-t)
4. Press Enter from the 4.d-t screen and the initial value 200 will be displayed.
5. Use the Up/Down key to display the set value on the screen.
Note1)
6. Press Enter to set as 100sec. (200
100sec)
① Set by 1sec unit ranging from 1 sec to 200sec; the default is 200sec.
② When the overcurrent operating characteristic is set as ‘n-th’ or ‘th’, it is excluded from the setting menu.
7. Press Test/Reset to return to the display screen.
Overcurrent delay time setting
This menu is displayed only when the overcurrent operating characteristic is set as dEF (definite time).
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
Note 1) Upon initial setting, P-99 is displayed on the screen. Here, use the Up/Down key to change it into P-00 and press Enter. You are now ready for setting.
The DMPi main screen display (0.00A)
1. Press Enter from the main screen. (A-gr)
2. Press Enter from the A-gr screen. (1. PHR)
3. Press the Up-key menu from the 1.PHR screen to proceed to 16.gF.
4. Press Enter from the 16.gF screen and the initial value OFF will be displayed.
5. Here, use the Up/Down key to set the value. Press Enter to save the setting.
Note1) (OFF
0.1A)
① Set by 0.1A unit ranging from 0.1A to 3.0A; or OFF, 0.03A, or 0.05A. (the default is OFF)
6. Press Test / Reset to return to the display screen.
Ground fault operating value setting
This is a function to set the operating value of ground fault.
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
R
C
50%
120%
A
%
S
T
N
Содержание EMPR DMPi Series
Страница 2: ...Electronic Motor Protection Relays ...
Страница 34: ...DMPi Series LSIS Co Ltd 33 MEMO ...
Страница 60: ...GMP Series LSIS Co Ltd 59 MEMO ...
Страница 72: ...IMP Series MEMO LSIS Co Ltd 71 ...
Страница 98: ...MMP Series MEMO LSIS Co Ltd 97 ...
Страница 107: ...106 Electronic Motor Protection Relays MEMO ...