4.1.11
Uploading configuration file to Alpha-Log
Watch the following video tutorials related to the topics of this chapter.
#
Title
YouTube link
QR Code
22
Alpha-Log: Uploading
configuration
Alpha-Log #22 - Uploading configuration -
YouTube
Delivery of the configuration file can be obtained in three different ways: direct SSH connection via Ethernet
or Wi-Fi, using USB pen drive, or using a FTP server set for this purpose.
4.1.11.1
Sending via SSH connection
Alpha-Log supports SSH. SSH (
Secure Shell
) is an encrypted protocol that allows the user to safely access the
devices connected into the same network.
In the guided transmission procedure of 3DOM’s configuration, set
following parameters up:
➢
Default communication type:
Connection using SSH protocol
➢
Instrument IP address (the current one)
➢
Port
Fig. 20
–
SSH connection to Alpha-Log with factory IP address example
To know the Alpha-
Log’s IP address, see
If the instrument does not have an IP address or it isn’t
in the same network as the PC, it is possible to send the configuration through a USB pen drive or check the
mode through FTP server.
4.1.11.2
Sending via USB pen drive
If Alpha-
Log isn’t connected to a network or to the
Internet, using a USB pen drive formatted with file system
FAT32 that has at least 2 MB of free available space to update the instrument configuration may be useful.
In this case, proceed as follows:
1.
Insert the USB pen drive into the PC.
2.
In 3DOM’s transmission procedure, select
Save on a local USB pen drive
.
3.
Safely eject the USB pen drive from the PC and insert it in one of Alpha-
Log’s USB ports
(3)
.
4.
Using the instrument buttons, enter
Pen drive
from the
ADVANCED FEATURES
menu.
5.
Select
Download config
and follow the instructions displayed.
6.
Select
Unmount
and follow the instructions displayed to remove the USB pen drive.