Communication port
: it is the serial port used for connection to one or more slave sensors.
➢
Speed
: it is the serial port communication speed (must be same speed set on the slave sensor).
Default= 9600 bps.
➢
Parity
: it is the parity used in communication. Default= None.
➢
Stop bits
: it is a communication parameter. Default= 1.
➢
Timeout
: it is the protocol waiting time after sending a request. Default= 1000 ms.
➢
Retries
: it is the number of attempts to send the request after a timeout without reply. Default= 2.
During the configuration, the Modbus RTU parameters for reading the data must also be specified. Refer to
the sensor documentation for this.
The Modbus RTU parameters are as follows:
➢
Network address
: it is the sensor address.
➢
Command
: it is the data request command to the sensor. It can be
Read Holding Register
or
Read
Input Register
according to the sensor specifications.
➢
Register
: it is the register containing the data to be read. The first register starts from the address
0x0000.
➢
Data format
: it is the format of the data produced by the sensor. Alpha-Log supports the following
formats:
o
Floating
: two 16-bit floating point registers. The byte ordering is defined by the
Order of
bytes
parameter
.
o
Integer16
: 16-bit unsigned register.
o
Integer 16s
: 16-bit signed register.
o
Integer32
: two consecutive unsigned 16-bit registers.
o
Integer32s
: two consecutive 16-bit signed registers.
➢
Scale factor
: for the integer data format, 16 or 32 bits, with or without sign, it is possible to specify
the division factor of the data to obtain a floating value.
➢
Order of bytes
: in case the sensor has floating type data format, it is possible to define the ordering
of the 4 bytes ABCD that make up the data:
o
ABCD
: default endian.
o
DCBA
: little endian.
o
BADC
: big endian.
o
CDAB
: reverse endian.
➢
Define error value
: if set to Yes, it enables the parameter
Error value
.
➢
Error value
: is the value that the measure assumes in the event of an error. The default value
is -99999.