XDesignerPlus Ver2.0 Communication Manual

5  /  13

Don't use overlapping IP address in unit network.

Item

Contents

Note

TCP/IP setting

High speed 

link station number

  0

Set station number when it communicated to high 

speed  between  XGT  PLC  FEnet  I/F  module  and 

module.

Media

AUTO

Select media.

IP address

192.168.0.51

Set IP address of FEnet I/F module.

Required 

setting

Subnet mask

255.255.255.0

Subnet mask

Gateway

192.168.0.1

Gateway address(Router address)

DNS server

0.0.0.1

Domain name server

DHCP

OFF (default)

If you use automatically assigned IP, check "ON".

Required 

setting

Receive Wait time

15 (default)

Personal  connection 

unit

3 (default)

Maximum  number  of  private  service  that  can 

connect simultaneously.

Driver(server) setting

Driver

XGT server

Required 

setting

Host table setting

Unable

Host table

OFF

Module  of  registered  IP  address  is  only  admitted 

connection to FEnet I/F.(If it is unable, unregistered 

Required 

setting

(2) External device setup

Run "XG-PD Editor" program for communication setting and set as below. 

If you want to change communication interface, modify refer to PLC manual. 

1.

 Run File > New File”. Select CPU Type and push OK button refer to “1. system configuration”.

2.

 Connect CPU LOADER port of XGT Series and serial port of PC by serial cross cable.

(If there is USB port in CPU, connect USB.)

3.

 Run [Online] > [Connection settings] menu. Select [Connection settings->Type] and click [Connect] button.

4.

 Run [Online] > [I/O Information] and read slot number. Run [Online] > [Read Parameter] and read parameter information of slot 

of communication card.

5.

 Double click slot of FEnet card in [Project Window], show dialog box of [Default settings].

Set [Connection] and [Run Mode] as below and click [OK].

Содержание XBC-D 32H

Страница 1: ...l devices serial signal types connection configurations Refer this section to select the right system configuration 2 Selection of TOP External device Page3 A section for selecting a Top model and the external device 3 Example of system setting Page 4 A section for explaining examples to connect communications of TOP to External Device Select the correct example in your case according to 1 System ...

Страница 2: ...ting ex 1 4 page Ethernet TCP setting ex 2 6 page 1 System configuration System configuration of TOP and LS Industrial Systems Co Ltd XGT XGK XGB XBC XBM Series is as below 1 Twist pair cable It means STP shield twist pair cable or UTP shieldless twist pair cable category 3 4 5 It can connect to hub transceiver etc according to network composition and use direct cable in this case Connection confi...

Страница 3: ... model which is communicated with external device External Device Vendor Select vendor of the external device which is communicated with TOP Select LS Industrial Systems Co Ltd PLC Select a model name of the external device which is communicated with TOP Select XGT XGK XGB XBC XBM Series FENET Check whether the external device you want to use is connectable or not in 1 System configuration 2 Selec...

Страница 4: ...r option XGT XGK XGB XBC XBM Series FENET IP Address PLC Type the IP address that the external device was given Reading port writing port Choose the port number that will be used for ethernet communication Please input the port number that GPPW issued 3 System setting Set Communication interface of TOP and external device as below 3 1 Example 1 Set your system as below 1 Network address TOP and ex...

Страница 5: ...T server Required setting Host table setting Unable Host table OFF Module of registered IP address is only admitted connection to FEnet I F If it is unable unregistered Required setting 2 External device setup Run XG PD Editor program for communication setting and set as below If you want to change communication interface modify refer to PLC manual 1 Run File New File Select CPU Type and push OK b...

Страница 6: ...XDesignerPlus Ver2 0 Communication Manual 6 13 client can t connect 6 Transfer setting contents to CPU at Online Parameter Write 7 Reset PLC at Online Reset Reset PLC ...

Страница 7: ... device setup Set the communication driver option XGT XGK XGB XBC XBM Series FENET IP Address PLC Type the IP address that the external device was given Reading port writing port Choose the port number that will be used for ethernet communication Please input the port number that GPPW issued 3 2 Example 2 Set your system as below 1 Network address TOP and external device must be same IP s three pl...

Страница 8: ...quired setting Host table setting Unable Host table OFF Module of registered IP address is only admitted connection to FEnet I F If it is unable unregistered client can t connect Required setting 2 External device setup Run XG PD Editor program for communication setting and set as below If you want to change communication interface modify refer to PLC manual 1 Run File New File Select CPU Type and...

Страница 9: ...XDesignerPlus Ver2 0 Communication Manual 9 13 6 Transfer setting contents to CPU at Online Write 7 Reset PLC at Online Reset PLC ...

Страница 10: ...d with COM2 1 port Serial Data Bit Setup Data Bit of PLC connected with COM2 1 port Serial Stop Bit Setup Stop Bit of PLC connected with COM2 1 port Serial Parity Bit Setup Parity Bit of PLC connected with COM2 1 port Time Out x100 mSec Setup Time Out of PLC connected with COM2 1 port Timeout waiting time for answer of PLC Send Wait x10 mSec Setup Send Wait of PLC connected with COM2 1 port Send W...

Страница 11: ...g time between response receiving next command request transmission from external device at 0 5000 x 1 mSec TOP IP Setup the IP address that TOP receives in the network Port Settings Ethernet Communication Ethernet Port Network setting Communication Interface MAC 00 15 ID 00 30 52 each device has different address Settings IP Address 192 168 0 50 Subnet mask 255 255 255 0 Gateway 192 168 0 1 Detai...

Страница 12: ...External device Name of CPU OK NG Name of communication device OK NG Protocol mode OK NG Other specified setting info OK NG IP Address Local Destination OK NG Port number Local Destination OK NG Subnet mask OK NG Gateway OK NG Address range confirm other docs OK NG 4 3 Communication diagnosis TOP Confirming interface setting condition between external devices Move to Menu by clicking the top side ...

Страница 13: ...0000 00 D65535 15 N00000 N21503 R W File Register R00000 00 R32767 15 R00000 R32767 R W File Register ZR00000 00 ZR65535 15 ZR00000 ZR65535 R W Item 32BIT 16BIT address D00100 D00100 D00101 Input data Hex 12345678 5678 1234 5 Available address The available address of device are as below Device address range might be different according to series type of CPU TOP Series are capable of supporting ma...

Отзывы: