![LS Industrial Systems SV-iS7 PLC Скачать руководство пользователя страница 137](http://html.mh-extra.com/html/ls-industrial-systems/sv-is7-plc/sv-is7-plc_user-manual_1943813137.webp)
Appendix 4 Common Area Parameter of iS7 Inverter
Appendix 4
-5
Address
Parameter
Scale
Unit
R/W
Detailed Description
BIT9
None
BIT8
None
BIT7
None
BIT6
None
BIT5
None
BIT4
Gate Drive Power Loss
BIT3
Watchdog-2 Error
BIT2
Watchdog-1 Error
BIT1
EEPROM Error
BIT0
ADC Error
BIT15
None
BIT14
None
BIT13
None
BIT12
None
BIT11
None
BIT10
None
BIT9
Auto Tunning Failure
BIT8
Keypad Lost
BIT7
encoder mis-connected
BIT6
encoder mis-mounted
BIT5
DB
BIT4
FAN Operation
BIT3
Lost command
BIT2
Inverter Overload
BIT1
Underload
0x0334
Warning
Information
- -
R
BIT0
Overload
0x0335
~0x033
F
Reserved -
-
-
-
0x0340
On Time Date
-
Day
R
Days when inverter is ON
0x0341
On Time Minute
-
Min
R
Minutes with total days on time subtracted
0x0342
Run Time Date
-
Day
R
Total days when the inverter operates the motor
0x0343
Run Time Minute
-
Min
R
Minutes with total days Run time subtracted
0x0344
Fan Time Date
-
Day
R
Total days when the fan operates
0x0345
Fan Time Minute
-
Min
R
Minutes with total days Fan time subtracted
0x0346
~0x034
9
Reserved -
-
-
-
0x034A Option
1
- -
R
0x034B Option
2
- -
R
0x034C Option
3
- -
R
0: None
1,2: Reserved
3: Profibus 4,5,6: Reserved
7: RNet 8,9: Reserved
10: PLC 20: External IO-1
23: Encorder
Содержание SV-iS7 PLC
Страница 46: ...Chapter 5 Input and Output Function 5 5 Load ...