11. Monitoring
11-7
SV-iC5
I56: When 17 {Fault display} is selected in I54 and I55, Multi-function output terminal and relay will
be activated with the value set in I56.
0 : FDT-1
Check whether the output frequency of the inverter matches the user-setting frequency.
Active condition: Absolute value (preset frequency - output frequency)
<=
Frequency Detection
Bandwidth/2
Group
LED Display
Parameter Name
Set
value
Min/Max
range
Factory
default
Unit
I/O group
I53
[Frequency
Detection
Bandwidth]
-
0/400
10.0
Hz
Cannot be set above Max frequency (F21).
When setting I53 to 10.0
1 : FDT-2
It activates when the preset frequency matches frequency detection level (I52) and FDT-1 condition
is met.
Active condition: (Preset frequency = FDT level) & FDT-1
Group
LED Display
Parameter Name
Set
value
Min/Max
range
Factory
default
Unit
I/O group
I52
[Frequency
Detection
Level]
-
0/400
30.0
Hz
I53
[Frequency
detection
bandwidth]
-
10.0
It cannot be set above F21- [Max frequency].
When setting I52 and I53 to 30.0 Hz and 10.0 Hz, respectively
25Hz
Freq.
setting
Freq.
MO
30Hz
50Hz
Run
command
15Hz
Freq.
setting
Freq.
MO
20Hz
40Hz
20Hz
40Hz
35Hz
Run
command
Содержание SV iC5 Series
Страница 8: ...Table of Contents viii SV iC5...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes...
Страница 136: ......
Страница 142: ......
Страница 143: ......