8)
Connect harmonic filter line side terminals L1, L2, L3
to power input protection
(current limiting fuses
– see below).
Cable wiring please refer to the remarks for the 4) load side cable wiring.
Note:
Finger guard must be installed in order to achieve IP 20 protection.
When the finger guard is not installed, LS Electric do not guarantee IP 20 protection.
9)
Fuse
HFS Harmonic filters need external over-current protection for compliance with UL/cUL standard.
Fuses and associated fuse holders must be UL listed and rated for 100kA SCCR supplies.
Please refer to requested fuse current ratings for UL class J and in full version user manual, where UL
compliance is not mandatory, for IEC class gG. The fuse rating is independent of the supply voltage.