LOYTEC CEA-709 Скачать руководство пользователя страница 39

L-Switch User Manual 

39 

LOYTEC  

Version 6.0 

 

LOYTEC electronics GmbH   

8.6  Technical Support 

LOYTEC  offers  free  telephone  and  e-mail  support  for  our  L-Switch  XP  product  series.  If 
none  of  the  above  descriptions  solves  your  specific  problem  please  contact  us  at  the 
following address: 

LOYTEC electronics GmbH 
Blumengasse 35 
A-1170 Vienna 
Austria / Europe 

email : 

 

[email protected]

 

web :

 

http://www.loytec.com

 

tel : 

+43/1/4020805-100 

fax : 

+43/1/4020805-99 

or 

LOYTEC Americas Inc. 
N27 W23957 Paul Road 
Suite 103 
Pewaukee, WI. 53072 
USA 

email:

 

[email protected]

 

web: 

http://www.loytec-americas.com

 

tel: 

+1/262/278 4370 

fax: 

+1/262/408 5238 

Содержание CEA-709

Страница 1: ...L Switch XP CEA 709 Router User Manual LOYTEC electronics GmbH...

Страница 2: ...R ANY OTHER APPLICATION IN WHICH IN THE FAILURE OF SUCH PRODUCT COULD CREATE A SITUATION IN WHICH PERSONAL INJURY OR DEATH MAY OCCUR LOYTEC MAKES NO REPRESENTATION AND OFFERS NO WARRANTY OF ANY KIND R...

Страница 3: ...rt 14 2 6 3 LS 11CB 2 Port 14 2 6 4 LS 13300CB 3 Port 15 2 6 5 LS 33300CB 3 Port 15 2 6 6 LS 13333CB 5 Port 16 2 6 7 LS 11333CB 5 Port 17 2 7 Wiring 17 3 Network Media 19 3 1 TP 1250 19 3 2 FT 10 20 3...

Страница 4: ...les 32 6 The L Switch XP in a Network 33 6 1 L Switch XP as Smart Switch 33 6 2 L Switch XP as Configured CEA 709 Router 34 6 3 Wink action 34 7 Updating the L Switch XP Firmware 35 7 1 Firmware Updat...

Страница 5: ...Time IP Internet Protocol IP 852 logical IP channel that tunnels CEA 709 packets according CEA 852 LSD Tool LOYTEC System Diagnostics Tool MAC Media Access Control MD5 Message Digest 5 a secure hash f...

Страница 6: ......

Страница 7: ...the L Switch XP can be configured via the network In addition to the Plug Play switch mode the L Switch XP can be operated as a standard configured CEA 709 router In this operating mode the L Switch...

Страница 8: ...types e g power line and FT Network monitoring and network management 1 2 Scope This document covers L Switch XP devices with firmware version 6 0 See Section 10 for differences between the different...

Страница 9: ...closure is 9 TE 1 TE 17 5 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 Status Button DIP Switch Console Connector Status LED Port LEDs Figure 1 L Switch XP multi port enclosure dime...

Страница 10: ...e ID of each port NIDx Unless stated otherwise all bar codes are encoded using Code 128 An additional label is also supplied with the L Switch XP for documentation purposes Internally the 3 Port LS xx...

Страница 11: ...n 6 0 LOYTEC electronics GmbH Figure 3 Internal assignment of NIDs on LS xxx00CB Figure 4 Example of internal NID order on LS xxx00CB Figure 5 Internal assignment of NIDs on LS xxxxxCB Figure 6 Exampl...

Страница 12: ...e DIP switch assignment is shown in Table 1 For details see Chapter 4 DIP Switch Function Factory Default 1 2 ON ON L Switch XP switch mode ON OFF L Switch XP repeater mode OFF ON L Switch XP subnet l...

Страница 13: ...mends using its LPOW 2415B power supply with the L Switch XP 2 6 Connecting Diagrams The L Switch XP provides screw terminals to connect to the network as well as to the power supply The screw termina...

Страница 14: ...0 Channel Port 1 15 Earth Ground 16 17 Power Supply do not connect terminal 17 to earth ground Table 5 L Switch XP Terminals LS 13CB 2 6 3 LS 11CB 2 Port Terminal Function 1 Earth Ground 2 3 CEA 709 A...

Страница 15: ...Channel Port 1 24 Earth Ground 25 26 Power Supply do not connect terminal 26 to earth ground Table 7 L Switch XP Terminals LS 13300CB 2 6 5 LS 33300CB 3 Port Terminal Function 1 6 NC 7 Earth Ground 8...

Страница 16: ...l Port 5 4 Earth Ground 5 6 CEA 709 A B of FT 10 Channel Port 4 7 Earth Ground 8 9 CEA 709 A B of FT 10 Channel Port 3 10 Earth Ground 11 12 CEA 709 A B of FT 10 Channel Port 2 13 Earth Ground 14 15 C...

Страница 17: ...Terminals LS 11333CB 2 7 Wiring Every network segment connected to the L Switch XP needs to be terminated according to the rules found in the specification of the transceiver see Chapter 3 Important...

Страница 18: ...Switch User Manual 18 LOYTEC Version 6 0 LOYTEC electronics GmbH 100 Port not in use Power Supply Figure 7 Connecting the L Switch XP LS 13333CB Figure 7 shows an L Switch XP where Port 5 is not used...

Страница 19: ...k termination LT 13 Figure 8 shows an example Figure 8 TP 1250 and FT 10 Network Termination If the collision less backbone mode recommended default behavior is disabled the L Switch XP TP 1250 ports...

Страница 20: ...nd of the bus LOYTEC recommends using its L TERM network terminators LT 13 LT 33 or LT 03 for network termination see Figure 9 Figure 9 FT 10 Network Termination 3 3 RS 485 The L Switch XP RS 485 port...

Страница 21: ...rs for the LONMARK TP RS485 39 channel 39 kbps are used RS 485 can only be used in a bus configuration and must be terminated on both ends The maximum stub length between the main bus and a single nod...

Страница 22: ...on address of a message to which port s the message has to be forwarded or whether it has to be forwarded at all Thus it isolates local network traffic e g in case of heavy loaded networks This is the...

Страница 23: ...lt all subnet or domain wide broadcasts are forwarded to all ports1 4 1 1 5 Unique Node ID Address Learning The L Switch XP has no learning strategy for unique node ID addresses Node ID addressed mess...

Страница 24: ...mode of the standard CEA 709 router differs from the L Switch XP repeater mode see Section 4 1 2 While the L Switch XP repeater mode is transparent and does not require any additional configuration th...

Страница 25: ...conds the next available port will be selected When the status button is released the Service Pin Message is sent out on the currently selected port If the L Switch XP is operated in smart switch mode...

Страница 26: ...repeater mode Table 11 Port LED patterns 5 3 Console The L Switch XP is equipped with a serial interface to display the results of the self test allow advanced configuration via a console menu upgrade...

Страница 27: ...CEA 709 port 5 FT Passed Starting CEA 709 networking Passed L Switch XP c LOYTEC electronics GmbH Mon Sep 10 08 11 41 2012 V6 0 0 Figure 15 Console messages during the boot phase The duration of a su...

Страница 28: ...interface console See Section 7 2 for detailed instructions Note If you select this option accidentally you can return to the main menu by sending a break signal In case your terminal program does no...

Страница 29: ...nfiguring the CEA 709 router mode CEA 709 Configuration Menu 1 Port 1 XF TP 1250 1250 kBit Port 2 FT Port 3 FT Port 4 FT Port 5 FT r Router configuration Configured Router DIP q Quit without saving x...

Страница 30: ...this menu Set router mode 1 Enable Configured Router Mode 2 Enable Smart Switch Mode 3 Set router configuration according to DIP switch Please choose Figure 21 Router mode configuration menu 2 Subnet...

Страница 31: ...ed using this menu option 5 3 6 Reset configuration load factory defaults This menu item allows resetting the device into its factory default state The following menu appears Reset Configuration Menu...

Страница 32: ...earing the L Switch XP status and statistic data Resetting the L Switch XP back to unconfigured state All this is done when the button is released Afterwards a reset is performed to let the changes ta...

Страница 33: ...ng the network cables the L Switch XP can be powered up and it will start its switching application When using a standard binding tool e g LonMaker bindings between nodes connected to different ports...

Страница 34: ...ter FT 10 Router FT 10 Router FT 10 Router FT 10 Router TP 1250 Figure 24 Internal structure of a 5 Port L Switch XP in configured CEA 709 router mode Each router must be commissioned separately The p...

Страница 35: ...any messages 7 1 Firmware Update via the Network Basically firmware downloads can be performed on every L Switch XP port However since the L Switch XP is not based on a Neuron Chip a new firmware imag...

Страница 36: ...that Figure 25 and Figure 26 do not necessarily show the proper product Press Download to start the download A progress bar as shown in Figure 26 can be seen Figure 26 Progress bar during firmware dow...

Страница 37: ...0 channel is used in standard backbone mode make sure that all L Switch XP devices have the collision less backbone mode disabled 8 2 One or more port LEDs are flashing red Problem One or more port LE...

Страница 38: ...o firmware update was attempted please contact LOYTEC support see Section 8 6 8 4 LonMaker cannot commission node Problem When adding a new node to a LonMaker project LonMaker receives the service pin...

Страница 39: ...lves your specific problem please contact us at the following address LOYTEC electronics GmbH Blumengasse 35 A 1170 Vienna Austria Europe email support loytec com web http www loytec com tel 43 1 4020...

Страница 40: ...use the enhanced statistic features of the L Switch XP with the LOYTEC system diagnostics tool LSD tool AN006E L Switch XP and LNS How to use the L Switch XP with LonMaker and other network management...

Страница 41: ...on the firmware version The L Switch XP can be used with firmware versions 3 0 and up Firmware Version Features 1 0 1 2 Final 1 2 0 3 0 3 1 4 2 6 0 Console Menu configuration firmware update Aging mec...

Страница 42: ...1100 mA 24 VAC Operating Temperature ambient 0 C to 50 C Storage Temperature 10 C to 85 C Humidity non condensing operating 10 to 90 RH 50 C Humidity non condensing storage 90 RH 50 C Enclosure Instal...

Страница 43: ...on LSD Tool Added application note on L Switch XP LonMaker shapes Updated application note on L Switch XP backbone mode Added application note on using L Switch XP devices with CEA 709 IP Routers Add...

Отзывы: