7 Updating the L-Switch XP 

Firmware 

The  L-Switch  XP  firmware  supports  remote  upgrade  over  the  network  and  the  serial 
console. 

To guarantee that the L-Switch XP cannot be destroyed due to a failed firmware update the 
L-Switch XP firmware consists of two images: 

 

Fall-back image 

 

L-Switch XP application image 

The fall-back image is write protected in flash memory and provides everything needed to 
talk to the L-Switch XP platform over the network. The L-Switch XP application image is 
designed to be updated over the network whenever there is a need to do so. 

The  fall-back  image  makes  sure  that  the  L-Switch  XP  comes  up  in  a  status  where  the 
maintenance software can at least talk to the L-Switch XP platform and can download a new 
L-Switch XP application image. 

When the L-Switch XP boots up with the fall-back image, all port LEDs are flashing red. In 
this state it does not forward any messages. 

7.1  Firmware Update via the Network 

Basically  firmware  downloads  can  be  performed  on  every  L-Switch  XP  port.  However, 
since  the  L-Switch  XP  is  not  based  on  a  Neuron  Chip  a  new  firmware  image  cannot  be 
downloaded with a standard tool. Rather, a designated tool, the LSD Tool (see Section 9), 
must  be  used.  See  the  LSD  Tool  documentation  for  details  on  how  to  download  a  new 
L-Switch XP firmware via the network. 

7.2  Firmware Update via the Console 

To  download  the  firmware  via  the  console  the  L-Switch  XP  must  be  connected  to  the 
RS-232 port of a PC via its console interface as described in Section 5.3. You will need the 
LOYTEC serial upgrade tool (LSU Tool), which can be downloaded from our homepage at 

www.loytec.com

Please make sure that the L-Switch XP console shows the main menu otherwise navigate to 
the main menu or simply reset the L-Switch XP. 

Double click on the *.dlc file that comes with the new firmware package. This should start 
the  LSU  Tool  and  load  the  firmware  image  referenced  in  the dlc file. Please note that the 
dlc file and the dl file must be stored in the same folder. The start window of the LSU tool 
is shown in Figure 25. 

Содержание CEA-709

Страница 1: ...L Switch XP CEA 709 Router User Manual LOYTEC electronics GmbH...

Страница 2: ...R ANY OTHER APPLICATION IN WHICH IN THE FAILURE OF SUCH PRODUCT COULD CREATE A SITUATION IN WHICH PERSONAL INJURY OR DEATH MAY OCCUR LOYTEC MAKES NO REPRESENTATION AND OFFERS NO WARRANTY OF ANY KIND R...

Страница 3: ...rt 14 2 6 3 LS 11CB 2 Port 14 2 6 4 LS 13300CB 3 Port 15 2 6 5 LS 33300CB 3 Port 15 2 6 6 LS 13333CB 5 Port 16 2 6 7 LS 11333CB 5 Port 17 2 7 Wiring 17 3 Network Media 19 3 1 TP 1250 19 3 2 FT 10 20 3...

Страница 4: ...les 32 6 The L Switch XP in a Network 33 6 1 L Switch XP as Smart Switch 33 6 2 L Switch XP as Configured CEA 709 Router 34 6 3 Wink action 34 7 Updating the L Switch XP Firmware 35 7 1 Firmware Updat...

Страница 5: ...Time IP Internet Protocol IP 852 logical IP channel that tunnels CEA 709 packets according CEA 852 LSD Tool LOYTEC System Diagnostics Tool MAC Media Access Control MD5 Message Digest 5 a secure hash f...

Страница 6: ......

Страница 7: ...the L Switch XP can be configured via the network In addition to the Plug Play switch mode the L Switch XP can be operated as a standard configured CEA 709 router In this operating mode the L Switch...

Страница 8: ...types e g power line and FT Network monitoring and network management 1 2 Scope This document covers L Switch XP devices with firmware version 6 0 See Section 10 for differences between the different...

Страница 9: ...closure is 9 TE 1 TE 17 5 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 Status Button DIP Switch Console Connector Status LED Port LEDs Figure 1 L Switch XP multi port enclosure dime...

Страница 10: ...e ID of each port NIDx Unless stated otherwise all bar codes are encoded using Code 128 An additional label is also supplied with the L Switch XP for documentation purposes Internally the 3 Port LS xx...

Страница 11: ...n 6 0 LOYTEC electronics GmbH Figure 3 Internal assignment of NIDs on LS xxx00CB Figure 4 Example of internal NID order on LS xxx00CB Figure 5 Internal assignment of NIDs on LS xxxxxCB Figure 6 Exampl...

Страница 12: ...e DIP switch assignment is shown in Table 1 For details see Chapter 4 DIP Switch Function Factory Default 1 2 ON ON L Switch XP switch mode ON OFF L Switch XP repeater mode OFF ON L Switch XP subnet l...

Страница 13: ...mends using its LPOW 2415B power supply with the L Switch XP 2 6 Connecting Diagrams The L Switch XP provides screw terminals to connect to the network as well as to the power supply The screw termina...

Страница 14: ...0 Channel Port 1 15 Earth Ground 16 17 Power Supply do not connect terminal 17 to earth ground Table 5 L Switch XP Terminals LS 13CB 2 6 3 LS 11CB 2 Port Terminal Function 1 Earth Ground 2 3 CEA 709 A...

Страница 15: ...Channel Port 1 24 Earth Ground 25 26 Power Supply do not connect terminal 26 to earth ground Table 7 L Switch XP Terminals LS 13300CB 2 6 5 LS 33300CB 3 Port Terminal Function 1 6 NC 7 Earth Ground 8...

Страница 16: ...l Port 5 4 Earth Ground 5 6 CEA 709 A B of FT 10 Channel Port 4 7 Earth Ground 8 9 CEA 709 A B of FT 10 Channel Port 3 10 Earth Ground 11 12 CEA 709 A B of FT 10 Channel Port 2 13 Earth Ground 14 15 C...

Страница 17: ...Terminals LS 11333CB 2 7 Wiring Every network segment connected to the L Switch XP needs to be terminated according to the rules found in the specification of the transceiver see Chapter 3 Important...

Страница 18: ...Switch User Manual 18 LOYTEC Version 6 0 LOYTEC electronics GmbH 100 Port not in use Power Supply Figure 7 Connecting the L Switch XP LS 13333CB Figure 7 shows an L Switch XP where Port 5 is not used...

Страница 19: ...k termination LT 13 Figure 8 shows an example Figure 8 TP 1250 and FT 10 Network Termination If the collision less backbone mode recommended default behavior is disabled the L Switch XP TP 1250 ports...

Страница 20: ...nd of the bus LOYTEC recommends using its L TERM network terminators LT 13 LT 33 or LT 03 for network termination see Figure 9 Figure 9 FT 10 Network Termination 3 3 RS 485 The L Switch XP RS 485 port...

Страница 21: ...rs for the LONMARK TP RS485 39 channel 39 kbps are used RS 485 can only be used in a bus configuration and must be terminated on both ends The maximum stub length between the main bus and a single nod...

Страница 22: ...on address of a message to which port s the message has to be forwarded or whether it has to be forwarded at all Thus it isolates local network traffic e g in case of heavy loaded networks This is the...

Страница 23: ...lt all subnet or domain wide broadcasts are forwarded to all ports1 4 1 1 5 Unique Node ID Address Learning The L Switch XP has no learning strategy for unique node ID addresses Node ID addressed mess...

Страница 24: ...mode of the standard CEA 709 router differs from the L Switch XP repeater mode see Section 4 1 2 While the L Switch XP repeater mode is transparent and does not require any additional configuration th...

Страница 25: ...conds the next available port will be selected When the status button is released the Service Pin Message is sent out on the currently selected port If the L Switch XP is operated in smart switch mode...

Страница 26: ...repeater mode Table 11 Port LED patterns 5 3 Console The L Switch XP is equipped with a serial interface to display the results of the self test allow advanced configuration via a console menu upgrade...

Страница 27: ...CEA 709 port 5 FT Passed Starting CEA 709 networking Passed L Switch XP c LOYTEC electronics GmbH Mon Sep 10 08 11 41 2012 V6 0 0 Figure 15 Console messages during the boot phase The duration of a su...

Страница 28: ...interface console See Section 7 2 for detailed instructions Note If you select this option accidentally you can return to the main menu by sending a break signal In case your terminal program does no...

Страница 29: ...nfiguring the CEA 709 router mode CEA 709 Configuration Menu 1 Port 1 XF TP 1250 1250 kBit Port 2 FT Port 3 FT Port 4 FT Port 5 FT r Router configuration Configured Router DIP q Quit without saving x...

Страница 30: ...this menu Set router mode 1 Enable Configured Router Mode 2 Enable Smart Switch Mode 3 Set router configuration according to DIP switch Please choose Figure 21 Router mode configuration menu 2 Subnet...

Страница 31: ...ed using this menu option 5 3 6 Reset configuration load factory defaults This menu item allows resetting the device into its factory default state The following menu appears Reset Configuration Menu...

Страница 32: ...earing the L Switch XP status and statistic data Resetting the L Switch XP back to unconfigured state All this is done when the button is released Afterwards a reset is performed to let the changes ta...

Страница 33: ...ng the network cables the L Switch XP can be powered up and it will start its switching application When using a standard binding tool e g LonMaker bindings between nodes connected to different ports...

Страница 34: ...ter FT 10 Router FT 10 Router FT 10 Router FT 10 Router TP 1250 Figure 24 Internal structure of a 5 Port L Switch XP in configured CEA 709 router mode Each router must be commissioned separately The p...

Страница 35: ...any messages 7 1 Firmware Update via the Network Basically firmware downloads can be performed on every L Switch XP port However since the L Switch XP is not based on a Neuron Chip a new firmware imag...

Страница 36: ...that Figure 25 and Figure 26 do not necessarily show the proper product Press Download to start the download A progress bar as shown in Figure 26 can be seen Figure 26 Progress bar during firmware dow...

Страница 37: ...0 channel is used in standard backbone mode make sure that all L Switch XP devices have the collision less backbone mode disabled 8 2 One or more port LEDs are flashing red Problem One or more port LE...

Страница 38: ...o firmware update was attempted please contact LOYTEC support see Section 8 6 8 4 LonMaker cannot commission node Problem When adding a new node to a LonMaker project LonMaker receives the service pin...

Страница 39: ...lves your specific problem please contact us at the following address LOYTEC electronics GmbH Blumengasse 35 A 1170 Vienna Austria Europe email support loytec com web http www loytec com tel 43 1 4020...

Страница 40: ...use the enhanced statistic features of the L Switch XP with the LOYTEC system diagnostics tool LSD tool AN006E L Switch XP and LNS How to use the L Switch XP with LonMaker and other network management...

Страница 41: ...on the firmware version The L Switch XP can be used with firmware versions 3 0 and up Firmware Version Features 1 0 1 2 Final 1 2 0 3 0 3 1 4 2 6 0 Console Menu configuration firmware update Aging mec...

Страница 42: ...1100 mA 24 VAC Operating Temperature ambient 0 C to 50 C Storage Temperature 10 C to 85 C Humidity non condensing operating 10 to 90 RH 50 C Humidity non condensing storage 90 RH 50 C Enclosure Instal...

Страница 43: ...on LSD Tool Added application note on L Switch XP LonMaker shapes Updated application note on L Switch XP backbone mode Added application note on using L Switch XP devices with CEA 709 IP Routers Add...

Отзывы: