I451 I GB D F E 10 16
4257Z010
G
B
LOCKED MODE
In this mode neither manual nor automatic operation can
be performed. This mode can be activated by two ways:
– Extracting the padlock slider
– Inserting the auxiliary manual handle, changing to 0
(OFF) position and activating the handle padlockable
lever.
UNIT LOCKING VIA PADLOCKABLE LEVER ACTIVATION
This padlock can be in any position according to
changeover switch I - 0 - II or switch - disconnector 0 - I.
remove
to lock
UNIT LOCKING BY AUXILIARY MANUAL HANDLE
This padlock is only allowed at 0 (OFF) position, once
locked, the handle cannot be removed from the
MU
.
The output signal in between terminals 8 and 9 is only activated when the unit is locked via padlockable lever activation.
ERROR LED
MU
has an integrated led for failure indication. It can be activated in any of the below situations:
− Failure due to movement under locked position: The unit shaft has moved with the unit in Locked mode.
− Failure due to final position not reached: The ongoing movement has not been finalized.
− Failure due to broken clutch: A shaft movement has been performed with auxiliary manual handle while the state was AUTO. (see annex 6).
NOTE: Once error led is activated, the
MU
remains locked.
MU
unlocking is only possible by switching OFF and ON power supply.
remove
to lock
ANNEXES
Annex 1: changeover switch references
MU
range is available for changeover switches in the 160 to 400 Amp range. Power supply
is 230VAC/DC.
Changeover switches I - 0 - II
3 P 3 P + N
A Code Code
160 GE0160E GE0160ET4
200 GE0200E GE0200ET4
200 GE0201E GE0201ET4
250 GE0250E GE0250ET4
315 GE0315E GE0315ET4
400 GE0400E GE0400ET4
Annex 2:
DIMENSIONS (mm)
Motorized unit
MU
230VAC/DC
A Code
160-200 GEX690C
250-400 GEX691C
250
76
90
145
43
8
103
30
7
5
68
12,5
15
7