P4-02 

Seuil ON 3 

10.00 

-9999.99 – 9999.99 

P4-02 

ON threshold 3 

10.00  

-9999.99 – 9999.99 

P4-03 

Seuil OFF 3 

5.00 

-9999.99 – 9999.99 

P4-03 

OFF threshold 3 

5.00 

-9999.99 – 9999.99 

P5-01 

Choix fonction entrée 1 

OFF 

OFF - Désactivé   

ON - Activé 
TAR - Sélection tarif  

CLEAr P - réinitialisation 
compteurs partiels 

CLEAr H - réinitialisation 
compteur horaire 

CLEAr d - réinitialisation 
demande max. 

   

P5-01 

Function for Input 1  

OFF 

OFF – Disabled 

ON - Enabled 
TAR – Tariff selection  

CLEAr P – Clear partial energy 
CLEAr H – Clear hour meter 

CLEAr d - Clear max demand 

P6-01 

Activation compteur 

horaire 1 

OFF 

OFF-ON-THR-INP 

P6-01 

Hour counter 1 enable 

OFF 

OFF-ON-THR-INP 

P6-02 

Activation compteur 
horaire 2 

OFF 

OFF-ON-THR-INP 

P6-02 

Hour counter 2 enable 

OFF 

OFF-ON-THR-INP 

P6-03 

Activation compteur 

horaire 3 

OFF 

OFF-ON-THR-INP 

P6-03 

Hour counter 3 enable 

OFF 

OFF-ON-THR-INP 

P7-01 

Activation mesures de la 
demande 

OFF 

OFF-ON 

P7-01 

Enable demand  
measurements 

OFF 

OFF-ON 

P7-02 

Calcul puissance réactive 

FUND 

TOT-FUND 

   

P7-02 

Reactive power 

calculation method 

FUND 

TOT-FUND 

TOT-FUND 

P8-01 

Adresse série nœud 

001 

001-255 

   

P8-01 

Serial node address 

001 

001-255 

P8.02 

Vitesse sérielle 

 

9600 

1200 

2400 
4800 

9600 

19200 

38400 

   

P8.02 

Serial speed 

9600 

1200 

2400 
4800 

9600 

19200 

38400 

P8-03 

Format des données 

8 bit – n  

8 bits - aucune parité 

8 bits - impairs 

8 bits - pairs 

7 bits - impairs  

7 bits - pairs 

   

P8-03 

Data format 

8 bit – n  

8 bit - no parity 

8 bit, odd 

8 bit, even 

7 bit, odd  

7 bit, even 

P8.04 

Bit d'arrêt 

1-2 

   

P8.04 

Stop bit 

1-2 

P8.05 

Protocole  

Modbus 

RTU 

Modbus RTU 

Modbus ASCII 

   

P8.05 

Protocol 

Modbus 

RTU 

Modbus RTU 

Modbus ASCII 

 
Description des paramètres

 

   

 
Parameter description 

P1-01

 – S'il est réglé sur 0000 (par défaut) la protection par mot de passe est 

désactivée. Tout autre réglage définit le mot de passe d'accès aux fonctions avancées. 

P1-02

 – Active l'affichage des énergies exportées. 

P1-01

 – If set to 0000 (default) the password protection is disabled. 

Any other setting defines the password to access to the advanced functions.  

P1-02

 – Enabling of exported energies viewing. 

P2-01

 – Sélection de la mesure à laquelle sont appliqués les seuils pour le compteur 

horaire 1. Voir le tableau 1. 

P2-02

 – Seuil d'activation du compteur horaire 1. 

Remarque 

: les mesures sont mises à 

jour et intégrées 1 fois par seconde. 

P2-03

 – Seuil de désactivation du compteur horaire 1. 

Remarque 

: les mesures sont 

mises à jour et intégrées 1 fois par seconde. 

Remarque : 

Si P2-02 >= P2-03, le compteur horaire s'active quand la mesure spécifiée par P2-01 
devient supérieure à P2-02 et se désactive quand elle redevient inférieure à P2-03 

(fonction de seuil maximal avec hystérésis). 
Si, au contraire, P2-02 < P2-03, le compteur horaire s'active quand la mesure spécifiée 

par P2-01 est inférieure à P2-02 et se désactive quand elle redevient supérieure à  
P2-03 (fonction de seuil minimal avec hystérésis).  

P3-01, P3-02

 et 

P3-03

 – Comme P2-01, P2-02 et P2-03, mais en référence au 

compteur horaire 2. 

P4-01, P4-02

 et 

P4-03

 – Comme P2-01, P2-02 et P2-03, mais en référence au 

compteur horaire 3. 

P5-01

 – Sélectionne la fonction de l'entrée programmable : 

OFF

 – Entrée désactivée. 

ON

 – Entrée activée (pour fonctions génériques comme l'activation du compteur 

horaire). 

Tar 

= Sélectionne le tarif pour le comptage de l'énergie (T1 / T2).  

CLEAr P 

= Met à zéro les compteurs d'énergie partiels 

CLEAr H 

= Met à zéro tous les compteurs horaires 

CLEAr d 

= Met à zéro la demande max.

 

P6-01

 – Définit le fonctionnement du compteur horaire 1 : 

OFF

 – Compteur horaire désactivé, il n'est pas affiché. 

   

P2-01

 - Selection of measure to compare with thresholds for hour counter 1. 

See table 1.

 

P2-02

 – Threshold for hour counter 1 activation. 

Note:

 The measurements are 

updated every 1 second. 

P2-03

 – Threshold for hour counter 1 deactivation. 

Note:

 The measurements are 

updated every 1 second. 

Note 

If P2-02 >= P2-03, then the hour counter activates when the measure defined by  
P2-01 is higher than P2-02 and deactivates when its value becomes less than P2-03 

(maximum limit with hysteresis).  
If P2-02 < P2-03, then the hour counter activates when the measure defined by P2-01 

is lower than P2-02 and deactivates when its value becomes higher than P2-03 
(minimum limit with hysteresis).  

P3-01, P3-02

 and 

P3-03

 – As P2-01, P2-02 and P2-03, referred to hour counter 2. 

P4-01, P4-02

 and 

P4-03

 – As P2-01, P2-02 and P2-03, referred to hour counter 3. 

P5-01

 – Selects the function of the programmable input: 

OFF

 – Input disabled. 

ON

 – Input enabled (to be used for general functions like hour meter enabling). 

Tar 

= Selection of energy tariff (T1 / T2).  

CLEAr P 

= Clears partial energy counters. 

CLEAr H 

= Clears all hour counters. 

CLEAr d 

= Clears max demand. 

P6-01

 – Defines the hour counter 1 operation: 

OFF

 – Hour counter disabled. It is not shown on the display. 

ON

   – The hour counter is incremented as long as the energy meter is supplied. 

THR

 – The hour counter is incremented as long as the threshold defined with 

parameters P2-01, P2-02 and P2-03 is active. 

Содержание DMED301MID

Страница 1: ...s Geräts befinden und vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 2 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme...

Страница 2: ... measurement accuracy is compliant with reference standard EN 50470 3 Class B while the reactive energy with IEC EN 62053 23 Class 2 In addition to energy metering it can measure further quantities which can be viewed on the backlight LCD display The DME D301MID has a standard 4U 72mm wide modular housing and is supplied with sealable terminal blocks Description Boîtier modulaire 4U 72 mm pour rai...

Страница 3: ...L2 L3 Hz Fréquence 00 0 h Part Compteur horaire hhhhh mm 00000 00 L1 L2 L3 kW d Puissance active moyenne demande sur 15 min 00 00 kW d Max puissance active moyenne demande max 00 00 Selection of readings By pressing the keys it is possible to select the readings on the display following the sequence in the table reported below Each measurement unit is indicated by the correspondent icon in the low...

Страница 4: ...ce of imported and exported energy The pulsing rate of the LED gives an immediate indication of the power flowing in every moment The pulse duration colour and intensity of the LED are compliant with the reference standards that define its utilisation in order to verify the accuracy of the energy meter Indication du débit d énergie Quand un appareil détecte un débit d énergie vers la charge l écra...

Страница 5: ...if 1 Énergie Réactive Exp L3 2 kvarh 1000 1BFCh Tarif 2 Énergie Active Imp L3 2 kWh 1000 1C00h Tarif 2 Énergie Active Exp L3 2 kWh 1000 1C04h Tarif 2 Énergie Réactive Imp L3 2 kvarh 1000 1C08h Tarif 2 Énergie Réactive Exp L3 2 kvarh 1000 0002h Tension de Phase L1 2 V 100 0004h Tension de Phase L2 2 V 100 Modbus address table By modbus function 03 or 04 the following measures can be read from the d...

Страница 6: ...e peut être utilisée pour la sélection entre deux tarifs T1 et T2 avec compteurs d énergie séparés la mise à zéro des compteurs partiels des compteurs horaires et de la demande max en activant l entrée l activation du compteur horaire 0006h L3 Phase Voltage 2 V 100 0008h L1 Current 2 A 10000 000Ah L2 Current 2 A 10000 000Ch L3 Current 2 A 10000 000Eh L1 L2 Voltage 2 V 100 0010h L2 L3 Voltage 2 V 1...

Страница 7: ... clearing of partial energy meters CLEAR h simultaneous clearing of all 3 partial hour counters if enabled CLEAR d clearing of max demand values if enabled SET DEF set all parameters to default values SETUP programming of parameters set up INFO revision and checksum of internal software ESC return to normal operation 5 To select a function press while the required function is displayed For clearin...

Страница 8: ...marque les mesures sont mises à jour et intégrées 1 fois par seconde Remarque Si P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 devient supérieure à P2 02 et se désactive quand elle redevient inférieure à P2 03 fonction de seuil maximal avec hystérésis Si au contraire P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 est inférieure à P2 02 e...

Страница 9: ...l includes the harmonic contribution same vale as TOT case P08 01 Serial address node fot the communication protocol P08 02 Transmission speed of the communication port P08 03 Data format 7 bit settings possible only with ASCII protocol P08 04 Stop bit number P08 05 Communication protocol selection P7 02 Sélectionne la méthode de calcul pour la puissance réactive TOT la puissance réactive inclut é...

Страница 10: ...tial exported reactive energy 47 kvarh L1 Part Énergie réactive L1 exportée partielle 47 kvarh L1 Part Partial exported L1 reactive energy 48 kvarh L2 Part Énergie réactive L2 exportée partielle 48 kvarh L2 Part Partial exported L2 reactive energy 49 kvarh L3 Part Énergie réactive L3 exportée partielle 49 kvarh L3 Part Partial exported L3 reactive energy 50 kW d Demande de puissance active 50 kW d...

Страница 11: ...nt Iref Ib 15A Curant maximal Imax 80A Max current Imax 80A Courant de démarrage Ist 60 mA Start current Ist 60 mA Précision Accuracy Énergie active EN 50470 3 Classe B Active energy EN 50470 3 Class B Conditions de fonctionnement Ambient conditions Installation Uniquement pour usage interne Mounting Indoor use only Température d utilisation 25 55 C Operating temperature 25 55 C Température de sto...

Страница 12: ...0 49 Nm 4 4lbin Connexion interface série Serial interface connections Type de bornes À vis fixes Type of terminals Screw fixed Nbr de sorties 2 Number of outputs 2 Nbr bornes 4 Number of terminals 4 Section conducteurs min max 0 2 1 3 mm2 24 16 AWG Conductor cross section min max 0 2 1 3 mm2 24 16 AWG Couple de serrage des bornes 0 15 Nm 1 7lbin Tightening torque 0 15Nm 1 7lbin Boîtier Housing Ex...

Отзывы: