HIGH SPEED COUNTER MODE 8 (DC VERSION ONLY)
The Mode 8 High Speed Counter can use either input terminals I01 or I02 for forward up-counting to 1 kHz maximum at 12VDC or 24VDC high
speed input signal. The selected Counter Coil (C01-C1F) will turn ON when the pulse count reaches the target “Preset ON” value and remain ON
until the pulse count reaches the target “Preset OFF” value. The counter will reset when the preceding rung is inactive. The table below describes
each configuration parameter for High Speed Counter Mode 8.
Symbol
Description
1
Counting Mode (8) high speed counting
2
High speed counting input terminal: I01 or I02 only
3
Counting interval time: 0~99.99 sec
4
Counter 'on' preset Value, range: 0~999999
5
Counter 'off' preset Value, range: 0~999999
6
Counter Coil Number (C01~C1F total: 31 counters)