I185 GB 06 15
LRX D01
101
Mode
Display
5
Address: 0003
Receive:
Write coil
data storage:
01 05 00 03 FF 00 CRC16
DRE0=65280(hex: FF00)
Send: 01 05 00 03 FF 00 CRC16;
Address: DR03=0001
Receive:
data storage:
01 05 00 01 FF 00 CRC16;
DRE0=65280(hex: FF00)
Send: 01 05 00 01 FF 00 CRC16
SLAVER VIA MODBUS RTU PROTOCOL
Function Description:
LRD can be communication controlled by the computer or other controller with the communication. PC and other controller can read and write
I/O and state, Function Block preset value. It also can use to read Function Block current value and control SG Run/Stop mode.
Hardware Configuration:
1. Line some LRD RS485 port A, B as show below.
2. Set LRD the LRD in the SET menu to No Remote IO.
3. Set LRD ID = 01~99, each of those LRD’s ID is different.
For the other informations, refer to the instruction I196 on www.lovatoelectric.com