Code
Beschreibung
Default
Wertebereich / Range
Code
Description
P1-01
Passwort
0000
0000 - 9999
Password
P2-01
Wahl Funktion Ausgang 1
10 PUL / kWh
OFF - Deaktiviert
Output 1 function
OFF - Disabled
1000 PUL / kWh
100 PUL / kWh
10 PUL / kWh
1 PUL / kWh
THR – Programmierbare Schwellenwerte
THR – Programmable thresholds
P2-02
Referenzmessung für Schwellenwert Ausgang 1
01
(siehe Tabelle 1)
Reference measure for output 1 threshold
kW
(see table 1)
P2-03
Schwellenwert ON 1
100.00
0.00 – 999.99
ON threshold 1
P2-04
Verzögerung Schwellenwert ON 1
5 sec.
0 – 9999 sec.
ON delay 1
P2-05
Schwellenwert OFF 1
50.00
0.00 – 999.99
OFF threshold 1
P2-06
Verzögerung Schwellenwert OFF 1
5 sec.
0 – 9999 sec.
OFF delay 1
P3-01
Wahl Funktion Ausgang 2
OFF
OFF - Deaktiviert
Function of output 2
OFF - Disabled
1000 PUL / kWh
100 PUL / kWh
10 PUL / kWh
1 PUL / kWh
THR – Programmierbare Schwellenwerte
THR – Programmable thresholds
P3-02
Referenzmessung für Schwellenwert Ausgang 2
01
(siehe Tabelle 1)
Reference measure for output 2 threshold
(see table 1)
P3-03
Schwellenwert ON 2
100.00
0.00 – 999.99
ON threshold 2
P3-04
Verzögerung Schwellenwert ON 2
5 sec.
0 – 9999 sec.
ON delay 2
P3-05
Schwellenwert OFF 2
50.00
0.00 – 999.99
OFF threshold 2
P3-06
Verzögerung Schwellenwert OFF 2
5 sec.
0 – 9999 sec.
OFF delay 2
P4-01
Wahl Funktion Eingang 1
OFF
OFF - Deaktiviert
Function for Input 1
OFF - Disabled
ON - Aktiviert
ON - Enabled
TAR - Tarifwahl
TAR - Tariff selection
CLr Part - Rücksetzen der Teilzähler
CLr Part - Clear partial energy
CLr Hr - Rücksetzen des Stundenzählers
CLr Hr - Clear hour meter
CLr dE - Rücks. max Demand
CLr dE - Clear max demand
P5-01
Aktivierung Stundenzähler
OFF
OFF-ON-THR1-THR2-INP
Hour counter enable
P5-02
Aktivierung Messungen Demand
OFF
OFF-ON
Enable demand measurements
TABELLE DER SETUP-PARAMETER
SETUP PARAMETER TABLE
PARAMETER DESCRIPTION
P1-01
– If set to 0000 (default) the password
protection is disabled.
Any other setting defines the password to
access to the advanced functions.
P2-01
– Defines the function of the static
output 1 from the following list:
OFF
- Disabled
1000 PUL …1 PUL
– Static output 1 operates
as a pulse emitter for active energy count.
These selections define the number of pulses
sent for every kWh.
THR
– The static output 1 becomes an alarm
threshold for maximum or minimum limit,
depending on values programmed in P2-03
and P2-05.
If P2-03 >= P2-05, then output activates when
the measure defined by P2-02 is higher than
P2-03, end de-activates when its value
becomes less than P2-05 (maximum limit with
hysteresis).
If P2-03 < P2-05, then output activates when
the measure defined by P2-02 is lower than
P2-03, end activates when its value becomes
higher than P2-05 (minimum limit with
hysteresis).
PARAMETER-BESCHREIBUNG
P01-01
– Bei Einstellung auf 0000 (Default) ist
der Passwortschutz deaktiviert. Jede andere
Einstellung definiert das Zugangspasswort zu
den erweiterten Funktionen.
P2-01
– Definiert die Funktion des
programmierbaren statischen Ausgangs 1:
OFF
- Deaktiviert
1000 PUL …1 PUL
– Der statische Ausgang 1
dient als Impulsgeber für die Zählung der
Wirkenergie. Mit diesen Auswahlen wird die
Impulszahl pro kWh definiert.
THR
– Dient zur Programmierung des
Ausgangs 1 als oberer oder unterer Alarm-
Schwellenwert, je nach den in P2-03 und P2-
05 eingestellten Werten.
Wenn P2-03 >= P2-05 wird der Ausgang
aktiviert, sobald die von P2-02 vorgegebene
Messung > P2-03 ist, und er wird deaktiviert,
sobald sie wieder < P2-05 ist (Funktion oberer
Schwellenwert mit Hysterese).
Wenn hingegen P2-03 < P2-05, wird der
Ausgang aktiviert, sobald die von P2-02
vorgegebene Messung < P2-03 ist, und er wird
deaktiviert, sobald sie wieder > P2-05 ist
(Funktion unterer Schwellenwert mit Hysterese).