P03 – PASSWORD Default Range
P03.01
Enable password OFF OFF-ON
P03.02
User level password 1000 0-9999
P03.03
Advanced level password 2000 0-9999
P03.04
Remote control password OFF 0-9999
I456
GB
I
04
17
11
G
B
P01 – GENERAL UoM Default Range
P01.01
Motor nominal current In A 30.0 (100%Ie) 15.0…30.0 (50…100%Ie)
P01.02
Max (starting) current limit ILt %In 300 150…700
P01.03
Initial acceleration step % 10 0…100
P01.04
Acceleration ramp sec 10 1…120
P01.05
Deceleration ramp sec OFF OFF / 1…120
P01.06
End of deceleration threshold % 20 0…100
P01.07
Kick start % OFF OFF / 50…100
P01.08
Motor nominal cos
0.80 0.50…1.00
P01.01
– Motor nominal current rating. The range of settings in A depends on the ADXL size, but for all models ranges from 50% to 100% of the soft starter's rated current Ie.
P01.02
– Maximum limit current delivery during starting, as % of nominal motor current In. Given that the currents of the three phases are not balanced during starting, this limit considers the highest of the three
phases, i.e. L2 (phase connected directly). The maximum value may not exceed 550% of the soft starter's maximum current. For example: with a 25A motor on the ADXL 0030 600, the maximum current
limit Ilt is 550% of 30A = 165A, which is the 660% of the motor nominal current.
P01.03
– Initial acceleration step, delivered immediately after start. This step may refer to the torque or voltage, depending on whether torque or voltage mode is active. It must be set in such a way that the motor
starts running slowly immediately after the start command.
P01.04
– With torque control enabled (P05.01 = ON), this parameters determines the time required to reach 100% motor torque, and thus sets the acceleration ramp slope. If the torque demand from the load is less
than 100%, the time required to deliver it will be shorter in proportion, to keep the slope constant. If voltage ramp mode is enabled, on the other hand (P05.01 = OFF), since 100% of the voltage is
independent of the load, the time needed will always be constant.
P01.05
– Same concept as the previous parameter, for the deceleration ramp.
P01.06
– Final deceleration step. When the descending ramp reaches this level of torque or voltage, the motor is powered off.
P01.07
– If enabled, defines the voltage applied instantly after the start, for a period of 200ms. This gives an initial pulse of torque to the machines jammed on starting.
P01.08
– The nominal motor cos
. This is used to calculate the nominal maximum torque.
P02 – UTILITY UoM Default Range
P02.01
Language ENG (English) ENG
ITA
FRA
ESP
POR
DEU
P02.02
Temperature unit of measurement °C °C / °F
P02.03
Low backlight delay sec 60 5-600
P02.04
Default measure return sec 60 OFF / 10-600
P02.05
Default measure CURRENT CURRENT
CURRENT %
TORQUE
VOLTAGE
P02.06
Keyboard start/stop OFF OFF/ ON
P02.07
Phase current visualization OFF OFF / ON
P02.01
– Language selection for text on display.
P02.02
– Defines the unit of measurement for the temperature.
P02.03
– Low display backlighting switch delay.
P02.04
– Reset to default page delay when buttons are not pressed. If set to OFF the last manually selected page will always remain on the display.
P02.05
– Default page shown on the display when it is switched on and after the delay.
P02.06
– Enables motor start/stop from the front keypad. The STOP input terminal must be connected to the common (run enable). The START button must be held down for 2 sec.
P02.07
– Enables display of the three individual phase currents.
P03.01
– If set to OFF, password management is deactivated; the access to the settings and the command menu is free.
P03.02
– With P03.01 active, value to be specified to activate User level access. See the chapter Password-protected access.
P03.03
– As P03.02, referred to Advanced level access.
P03.04
– If set to a numeric value, it becomes the code to be specified via serial communication line before being able to send remote controls.
PARAMETER TABLE