Direct Calibration - Full Scale Setting
This is when you connect the meter to your system and make the meter read what
you want it to, at 2 different points.
This is the preferred calibration method, because
it allows you to calibrate the system as a whole.
How to do direct calibration:-
If you have not done so before, please select Direct Calibration mode from
the previous page.
First we recommend you set the
FULL SCALE
calibration ...
Lockout Switch must be OFF
Display shows
direCt
followed
by
SEt Hi
Press 3 seconds
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press OK. Apply the highest
calibration signal you can achieve,
ideally 100% of system capacity.
You can use less, but you will get better
accuracy with higher signals.
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press for 3 seconds
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
You can now set the display value you
want to see - use DIGIT to select each
digit in turn, and the UP or DOWN arrow
to increase or decrease each digit’s
value, as required.
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
1
2
3
4
5
Press Set2 for 3 seconds. You can now
set your decimal point position using
the UP or DOWN buttons.
Press OK when done.
Done!
This feature is available in Easy and Advanced Modes