background image

Wiring other LED-based crossing signals (including Walthers) 

If  you  are  using  another  brand  of  LED-based  crossing 
signals,  or  are  scratch-building  your  own,  you  MUST  wire 
them  in  a  common  anode  (positive)  manner. 

NOTE:  some 

manufacturers use a black wire for the common wire but that 
does NOT mean that it is a negative or ground wire!

 Figure 2 

at  right shows  you how to  wire ONE single-sided  signal; if 
you are using multiple signals, or dual-sided signals, simply 
duplicate the wiring shown for the additional LEDs. Each of 
the 

Grade Crossing Pro/2’s

 signal outputs can handle loads 

up  180mA  (~12  LEDs).  Note  that  EACH  LED  connection 
requires a current limiting resistor. The value of the resistor 
is dependent upon the voltage applied to the 

Grade Crossing 

Pro/2

. You can use Table 1 above to determine the minimum 

resistor value. Note that some of the resistors can be ¼ watt 
whereas others must be ½ watt. You can always substitute a 
½  watt  resistor  for  a  ¼  watt  resistor  but  you  CANNOT 
substitute a ¼ watt resistor for a ½ watt resistor! 

common anode

 

 

Figure 2 – Wiring LED-based crossing signals

 

 

 

Wiring bulb-based crossing signals (e.g. NJ International) 

Crossing  signals  constructed  with  bulbs  do  not  have  a 
polarity  like  LED-based  signals  do.  However,  some  bulb-
based signals may be pre-wired with a common wire. If your 
signal  does  not,  then  you  will  simply  create  a  common 
connection  from  one  lead  of  each  bulb  (it  doesn’t  matter 
which lead is used). Figure 3 at right shows you how to wire 
ONE  single-sided  bulb-based  signal.  The 

Grade  Crossing 

Pro/2

  will  support  two  dual-sided  signals;  if  you  are  using 

multiple  signals,  or  dual-sided  signals,  simply  duplicate  the 
wiring  shown  for  the  additional  bulbs.  Note  that  current 
limiting resistors are shown. These are only required  IF  the 
voltage provided to the 

Grade Crossing Pro/2

 is greater than 

the  rating  on  the bulbs;  most  bulbs  are  rated  at  12V  AC or 
DC but you should check the instructions that come with the 
signal.  If  the 

Grade  Crossing  Pro/2

 voltage  source  exceeds 

the bulb rating then add current limiting resistors as shown; 
we recommend a value of 100Ω, ¼ watt.  

 

Common

 

 

Figure 3 – Wiring bulb-based crossing signals 

 

 

 

Flashing effects (True Lamp2 and Flash Rate) 

As shown in the table on page 2 the 

Grade Crossing Pro/2

 has two configuration switches related to the crossing flasher 

outputs (LO and RO). The first is TRUE LAMP2. When this switch (#2) is in the ON position the LO and RO outputs will 
fade on and off which emulates older prototype crossing signals (when they used light bulbs). When this switch is OFF the 
LO and RO outputs will simply turn on and off during the flashing activity; this setting emulates newer prototype crossing 
signals which may use LEDs. If you are using bulb-type model railroad crossing signals we strongly suggest that you keep 
this switch OFF.  
The other flashing effect is the flash rate itself. The normal flash rate is selected when the FLASH RATE switch (#5) is in the 
OFF position. If you prefer the faster (2X speed) rate you MUST have BOTH the FLASH RATE switch in the ON position 
AND have the TRUE LAMP2 switch in the OFF position. As such you CANNOT have the faster flash rate and the signal 
on/off fading effect at the same time. 

 

End-of-Gate (EOG) LED 

The 

Grade Crossing Pro/2

 has a separate output (EOG) which can be used to turn on an LED wired to the end (tip) of a 

crossing gate. Like the prototype crossing gates, this output will be active (on) whenever the signals are flashing. It will be on 
steady (the True Lamp2 configuration switch setting does not affect it). You will wire this LED just like the LO or RO LEDs 
shown in Figures 1 and 2. Don’t forget the current limiting resistor! This output can handle loads up 180mA (~12 LEDs). 

Содержание GCP/2

Страница 1: ...IR4 if you want to change types The board is also offered without sensors version GCP 2 X for use with other brands of external detectors The infrared detection method has been improved and no longer...

Страница 2: ...2 is in sensor setup mode TRUE LAMP2 Signals don t fade on off like modern signals Signals fade on and off like older signals SEN TYPE Sensors are photocells or external current detectors Sensors are...

Страница 3: ...required IF the voltage provided to the Grade Crossing Pro 2 is greater than the rating on the bulbs most bulbs are rated at 12V AC or DC but you should check the instructions that come with the sign...

Страница 4: ...iring Tomar example NOTE You must check the instructions for your gate motor to determine the maximum voltage that the motor can accept For example Tomar uses Circuitron s Tortoise which has a maximum...

Страница 5: ...them this will allow the Grade Crossing Pro 2 to still properly detect a train that has stopped over any photocell with the gap between cars over a photocell EN EF WN WF Figure 6 Photocell wiring Pho...

Страница 6: ...the ties and roadbed Figure 8a Figure 8b Using across the rails infrared With this sensor mode and physical arrangement a train is detected when the infrared IR beam is broken by the train The IR comp...

Страница 7: ...f the four photocell sensitivity adjustment pots NOTE The four adjustment pots have NO affect when using either infrared sensor mode Do the following after you have connected power see page 9 to the b...

Страница 8: ...the SPKR outputs as shown in Figure 13b You can adjust the volume of the bell sound using the potentiometer labeled VOLUME next to the SPKR terminals Figure 13a Location for bell module 8 Figure 13b...

Страница 9: ...re flashing ON OFF OFF Rings continuously while signals are flashing ON OFF ON Stops ringing as the train clears but before flashing stops ON ON OFF Only rings while gates are lowering or raising ON O...

Страница 10: ...The problem with this implementation is that the Grade Crossing Pro 2 cannot differentiate between two trains traveling in opposite directions on different tracks As such it could easily get confused...

Страница 11: ...no train is present then you will probably see one or more of the red sensor LEDs lit up on the Grade Crossing Pro 2 board You may have the IR components sitting too high Make sure they are no higher...

Страница 12: ...e 2 If the product has been altered in any way e g soldering to the circuit board 3 If the current or voltage limitations of the product have been exceeded Requests for warranty service must include a...

Отзывы: