101+ DELAYED EGRESS
MAGNETIC LOCKING SYSTEM
7
FORM 10111 Rev. C
04/11/2002
5. SECURE MOUNTING PLATE
Using the Mounting Plate as a template, drill the four (or eight for 101+DB)
remaining mounting holes.
If using #10 self-tapping, flat-head screws drill 5/32" dia. holes and drive
four screws tight.
If using #10-24 flat head machine screws, drill and tap for #10-24 threads
and tighten four screws.
CAUTION:
If the frame is wood it is critical that the screws used secure the
mounting plate to the
structure
of the frame. It is the responsibility of the
installer to provide sufficient reinforcement for
a safe installation.
6. SECURE MAGNET TO MOUNTING PLATE
Install the electromagnet to the mounting plate using the two 1/4-20 x 2" socket head
cap screws with a hex key. Firmly tighten the screws. Pass wiring through hole in top
of magnet and through access hole on circuit board side of magnet as shown below.
Drive in anti-tamper plugs using a rubber mallet. (It is advisable to wait until the mag-
net is wired and tested before installing anti-tamper plugs in case the magnet position
must be adjusted.)
NOTE: For 101-2+ see wiring information on page 11 to wire between units.
8. FASTEN ELECTRONICS COVER AND LOCK GUARD
After wiring and programming (or if it is to be done later) fasten
the electronics cover(s) and lock guard(s) to the magnet. After
verifying that the unit works correctly install anti-tamper plugs, if
desired. Note that they will need to be drilled out if the lock
must be removed or adjusted.
7. MAKE FINAL WIRING CONNECTIONS, SET DIPSWITCHES, AND PROGRAM LOCK
(SEE WIRING AND PROGRAMMING BEGINNING ON PAGE 8)
Refer to the wiring and programming section of this manual. If wiring and programming is to be done by someone else(besides the person doing the mechanical installa-
tion) please make sure that this manual is given to that person. DO NOT DISCARD THIS MANUAL. IT IS IMPORTANT THAT IT BE GIVEN TO THE OWNER OR
BUILDING MAINTENANCE MANAGER FOR REFERENCE AFTER INSTALLATION.
101+DB
101+DB
101+DB