SYNC PUMP RECOMMENDATION TABLE

Temperature Rise

Temperature Rise

Temperature Rise

Temperature Rise

20°F 

Δ

 T

25°F 

Δ

 T

30°F 

Δ

 T

35°F 

Δ

 T

Boiler

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Rate

Loss

Rate

Loss

Rate

Loss

Rate

Loss

SBN1000

GPM

Ft/Hd

N/A

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

55.0

31.0

44.0

22.0

38.0

18.0

32.0

13.0

Boiler

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Rate

Loss

Rate

Loss

Rate

Loss

Rate

Loss

SBN1300

GPM

Ft/Hd

N/A

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

65.0

30.0

52.0

20.0

45.0

16.0

37.0

11.0

Boiler

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Flow

Head

Pump

Rate

Loss

Rate

Loss

Rate

Loss

Rate

Loss

SBN1500

GPM

Ft/Hd

N/A

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

GPM

Ft/Hd

PUM30001

74.0

33.0

60.0

23.0

51.0

18.0

42.0

12.0

This chart provides Pump recommendations for SYNC boilers for the Boiler Loop / Space Heating piping.

    Based on specific Temperature Rises, this chart includes calculated Gallon Per Minute flow rate, calculated Foot Head Loss and recommended Pump.
    The GPM, Ft/Hd and Pump selection is based on Primary / Secondary Boiler Loop piping of maximum 20 feet of straight pipe, 4 - 90° elbows and 2 - full port ball valves.
    See the Installation and Operation manual for more details including pipe diameters and piping diagrams.

Reminder: The SYNC boiler requires TWO pump, one for each heating module. 
                     The Pump recommendations listed above are for the individual heating module.