SDT/SET Installation & Operation Manual
Table 8E
First Hour Rating 200°F Boiler Loop Water (Universal Sizing, Upper Coil SDT Models)
First Hour Rating - 200°F Boiler Loop Water
(Universal Sizing - 45,000 - 295,000 Btu/hr / SDT065-119)
Boiler Supply Water
200
200
200
Circulator Flow GPM
5
8
12
16
20
5
8
12
16
20
5
8
12
16
20
Domestic Outlet
115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140 115 140
45,000
117 94
117
94
122 99 122 99
135 113 135 113
60,000
146 115 146 115
151 120 151 120
164 133 164 133
75,000
175 137 175 137
180 142 180 142
192 154 192 154
95,000
214 165 214 165 214 165
206 160 206 160 206 160
230 182 230 182 230 182
115,000
252 193 252 193 252 193 252 193
270 208 243 187 243 187
268 210 268 210 268 210
140,000
265 203 283 216 283 216 283 216 283 216 270 208 286 220 286 220 286 220
315 245 315 245 315 245 315 245
165,000
265 203 305 232 328 249 328 249 328 249 270 208 310 237 333 254 333 254 333 254 357 276 362 279 362 279 362 279 362 279
195,000
265 203 305 232 334 253 349 265 369 279 270 208 310 237 339 258 367 279 374 284 357 276 419 321 419 321 419 321 419 321
225,000
305 232 334 253 349 265 369 279
310 237 339 258 367 279 374 284
432
331
475 362 475 362 475 362
260,000
349 265 369 279
339 258 367 279 374 284
487 372 530 403 542 412
295,000
374 284
530 403 602 456
MAX BTU INPUT
121786
153207
168199
176783
188081
121786
153207
168199
176783
188081
162144
202222
231672
253492
291792
Boiler H
eat
ing Capacit
y
Model
SDT065 SDT080 SDT119
8
Performance Data
24
Note: Testing conducted with 50°F inlet cold water