30
9.5
MAXIMUM FLUE LENGTH - CONCENTRIC
When using the concentric flue system the maximum flue length for all models is 3 metres for horizontal
termination and 2 metres for vertical termination. For each 45° bend, 0.5 metres should be deducted from the
total length. For each 90° bend 1.0 metre should be deducted from the total length.
NOTE: The maximum flue run includes the length of the terminal.
9.6
MAXIMUM FLUE LENGTH – TWIN-PIPE
When using the twin-pipe flue system, the maximum flue length is 6 metres for both the inlet and exhaust pipe. For
each 45° bend, 0.5 metres should be deducted from the total length. For each 90° bend 1.0 metre should be
deducted from the total length.
NOTE: This is the maximum length for each pipe and not an aggregate for the two, for example a 3 metre
inlet cannot be combined with a 9 metre exhaust.
9.6.1
AIR RESTRICTION PLATE
The following restriction plate should be inserted if required:
LBF151/171 No Restriction Plate required.
LBF221 Ø 52mm Restriction Plate required.
LBF301 Ø 52mm Restriction Plate required if air and exhaust ducts less than 3m (no restriction plate is
needed for ducts over 3m).
LBF401 No Restriction Plate required.
The air restriction plates are supplied with the twin-pipe flue system and should be fitted as shown in
Figure 8.10.
.
Item
Description
1
Air Duct Transition Piece
2
Gaskets from Kit and Blank Plate
3
Restriction Plate
FIGURE 8.10
POSITION OF AIR RESTRICTION PLATE