25
9.3.4
VERTICAL CONCENTRIC FLUE FITTING DETAILS LBF151 – 401
FIGURE 8.5
VERTICAL CONCENTRIC FLUE KIT AKIT03 FOR LBF151-401
Kit Part Number
Description
Additional Components
Description
AKIT03
1000mm Vertical Concentric Flue Kit
AIPC10
60/100 Extension (Adjustable 1000mm)
Kit Components
1
60/100mm 90° Concentric Bend
2
60mm Flue seal
3
100mm Air Duct seal
4
Flue Gas Sampling Point Cap
5
60/100mm – 1m Vertical Terminal
6
60/100mm Transition piece with Sampling Point
1.
Determine the desired location for the flue terminal, taking into account minimum distances as detailed
in
Figure 8.1
,
Table 8.1
and the relevant British Standards.
2.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The
diameter of the hole should be no more than 10mm greater than the diameter of the air supply pipe of
the terminal.
NOTE:
The hole should be drilled from the outside to ensure that no damage is done to the roofing material.
Extra care should be taken to ensure that the hole is drilled vertically.
3.
Install the roof flashing and secure as appropriate.
4.
Carefully insert the roof terminal through the roof flashing and hole in the roof.
NOTE:
When inserting the roof terminal do not support or turn the terminal using the cap.
5.
Ensure the terminal is vertical using a spirit level.
6.
Fit the support bracket around the terminal and secure using appropriate fixings. Do not tighten the
support bracket.
7.
Fit the supplied transition piece (with sampling point) to the flue hood. Fit the 90° concentric bend to the
transition piece
8.
If an additional length of flue pipe is required to connect to the vertical terminal this should be measured
and cut accordingly. Due to the close tolerances in the flue system, it may be necessary to use a
twisting action to fit the joints together. No lubrication other than water should be used
9.
If no additional components are required measure and cut the Terminal length accordingly and insert
into the 90° bend.
10.
With all components in position, tighten any support brackets used.