Start-up
Check fl ame and combustion
(continued)
4. Place the boiler into the active position by pressing the
RIGHT SELECT [ON] key (FIG. 11-1, page 67).
5. Locate the pinhole button below the RESET button on
the display board (FIG. 11-1). Insert a thin wire (such
as a paper clip) into the hole and press the button once
and hold for 5 seconds to place the boiler into Service
Mode. In Service Mode the boiler will fi re at ignition
speed and will then modulate up to full fi re.
6. Insert the probe from a combustion analyzer into the
hole left by the removal of the fl ue temperature sensor.
7. Once the boiler has modulated up to full fi re, measure
the combustion. Th
e values should be in the range
listed in Table 10A below. Th
e CO levels should be less
than 150 ppm for a properly installed unit.
If the combustion is not within the specifi ed range,
reference the Troubleshooting Section of the Knight
XL Service Manual for possible causes and corrective
actions.
Set space heating operation
Determine controlling sensor
For space heating systems, the temperature control can be
based on one of three sensors; the inlet, outlet, or system
supply sensor. Th
e SMART SYSTEM control is programmed
at the factory to control the temperature of the outlet
sensor. Th
e control will automatically switch to the system
supply sensor once it is connected. If it is desired to base
the temperature control on the inlet sensor, the appropriate
parameter must be changed in the control. See the Knight XL
Service Manual for a detailed explanation of this procedure.
Verify space heat circulator mode
Th
e Space Heating Mode controls both the system pump
(if connected), and the boiler pump. When the SMART
SYSTEM control receives a space heating call for heat, it
turns on the system pump. If the boiler is not heating an
indirect DHW (Domestic Hot Water) tank, and the set
point is not met, it also turns on the boiler pump. Aft er the
space heating call for heat ends, the system pump continues
to run for a short period of time. Th
e system pump can be
programmed to run continuously, except during outdoor
shutdown. If the boiler pump was running, it continues to
run for a short period of time as well. Th
ese pump delays are
factory set to 30 seconds. If diff erent delays are desired, the
appropriate parameters in the control must be changed. See
the Knight XL Service Manual for a detailed explanation of
this procedure.
Adjust set point temperature(s)
Table 10A Flue Products Chart
8. Once the combustion analysis is complete, test the
safety
shutoff device by turning the manual shutoff
valve to the OFF position and ensuring that the boiler
shuts down and registers an alarm. Turn the manual
shutoff switch to the ON position and reset the control.
9. Turn the main power off to the boiler and replace the
fl ue temperature sensor into the fl ue pipe connection.
10. Place the boiler back into normal operation.
You must replace the flue gas
temperature sensor to prevent fl ue gas
spillage into the room. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
WARNING
Natural Gas
Propane
CO
2
O
2
CO
2
O
2
8.0% - 10%
3.0% - 6.5%
9.0% - 11%
4.1% - 6.9%
Please note that the brackets ([]) denote
screen status.
NOTICE
Th
e NAVIGATION dial may be used during normal
operation to adjust the space heating and tank set point
temperatures.
1. From the Status Screen press the NAVIGATION dial.
2. Turn the NAVIGATION dial counterclockwise to select
the appropriate set point.
3. Press the NAVIGATION dial to adjust the temperature.
4. Once the desired temperature is displayed, press the
RIGHT SELECT [SAVE] key.
5. If necessary repeat Steps 3 and 4 to make adjustments to
additional set points.
6. Press the RIGHT SELECT [HOME[ key to upload the
changes.
7. If the RIGHT SELECT [SAVE] key is not pressed, the
new settings will be discarded.