43
6
Hydronic piping
(continued)
Figure 6-9 Multiple Boilers - Multiple Temperatures
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment. Th
e installer must follow all manufacturer’s instructions for each system component. Th
e
installer is responsible for compliance with local codes.
NOTICE
CAUTION
Mixing valves are required for the protection of low temperature loops.
CAUTION
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler
output does not not exceed indirect water heater transfer capabilities.
Model
Number of Units
2
3
4
5
6
7
8
Manifold Pipe Sizes in Inches (mm)
400
2 1/2 (64)
3 (76)
3 1/2 (89) 4 (102) 4 (102) 5 (127) 6 (152)
501
3 (76)
3 1/2 (89)
4 (102)
5 (127) 5 (127) 6 (152) 6 (152)
601
3 1/2 (89) 4 (102)
5 (127)
5 (127) 6 (152) 6 (152) 8 (203)
701
3 1/2 (89) 5 (127)
5 (127)
6 (152) 6 (152) 8 (203) 8 (203)
801
4 (102)
5 (127)
5 (127)
6 (152) 8 (203) 8 (203) 8 (203)
Installation & Operation Manual