14
L o c h i n v a r
D E S I G N E R
’
S
G U I D E
E F F I C I E N C Y
+
B O I L E R
6 1 5 - 8 8 9 - 8 9 0 0
GAS SUPPLY
Safe operation of unit requires properly
sized gas supply piping (See TABLE G).
Gas pipe size may be larger than the
heater connection.
An internal gas pressure regulator is required
if upstream pressure exceeds 6 oz. (10.5"
water column), an intermediate gas
pressure regulator, of the lockup type,
must
be installed.
Installation of a union is suggested for
ease of service.
Install a manual main gas shutoff valve
with test plug, outside of the appliance
gas connection and before the gas valve,
when local codes require.
A trap (drip leg) should be provided in the
inlet of the gas connection to the unit.
High Altitude Applications
Atmospheric pressure decreases as the height
above sea level increases. At any altitude
above sea level, a cubic foot will contain less
gas than a cubic foot at sea level. Thus, the
heating value of a cubic foot of fuel gas will
decrease as height above sea level increases.
Specific gravity of a gas with respect to sea
level also decreases with altitude.
These changes in heating value and specific
gravity tend to offset each other. However, as
elevation above sea level is increased, there
is less oxygen per cubic foot of air. Therefore,
heat input rate should be reduced in an
appliance above 2000 feet. Ratings should
be reduced at the rate of 4 percent for each
1000 feet above sea level.
WATER CONNECTIONS
Inlet and Outlet Water Connections
For ease of service, install unions on inlet and
outlet of the boiler. The connection on the unit
marked “Inlet” should be used for return
water from the system. The connection on the
header marked “Outlet” should be connected
to the system supply. (See Boiler Piping
diagrams, Appendix A).
Lochinvar
NOTE:
Care should be
taken to measure
temperature rise
and maintain proper
water velocity in
the heat exchanger.
(TABLE H) – INLET GAS PRESSURE REQUIREMENTS
NATURAL GAS
LPG
Max. Allowable
10.5”
13”
(Inches-water column)
Min. Allowable
4.7”
8”
(Inches-water column)
EXAMPLE OF
HIGH
ALTITUDE
APPLICATIONS
For example, if a unit’s
input is 200,000 Btu/hr
at sea level, the rated
input at 4000 feet of
elevation can be calculated
by derating input 4%
per 1000 feet above
sea level.
[Btu/hr Input]
[1.00 - (Elevation/ 1000’
x 0.04)] = Btu/hr Input
at specified elevation.
[200,000][1.00 -
(4000’/1000’ x 0.04)] =
Btu/hr Input 4000’
elevation.
[200,000][0.84] =
168,000 Btu/hr Input
at 4000’ elevation.
(TABLE G) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron
Pipe Size, Inches
10
20
30
40
50
60
70
80
90
100
125
150
175
200
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total
system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
3/4
369
256
205
174
155
141
128
121
113
106
95
86
79
74
1
697
477
384
328
292
267
246
256
210
200
179
164
149
138
1-1/4
1,400
974
789
677
595
543
502
472
441
410
369
333
308
287
1-1/2
2,150
1,500 1,210 1,020
923
830
769
707
666
636
564
513
472
441
2
4,100
2,820 2,260 1,950
1,720 1,560
1,440 1,330
1,250
1,180
1,100
974
871
820
2-1/2
6,460
4,460 3,610 3,100
2,720 2,460
2,310 2,100
2,000
1,900
1,700
1,540
1,400
1,300
3
11,200
7,900 6,400 5,400
4,870 4,410
4,000 3,800
3,540
3,300
3,000
2,720
2,500
2,340
4
23,500 16,100 13,100 11,100 10,000 9,000
8,300 7,690
7,380
6,870
6,150
5,640
5,130
4,720
1.
2.
3.
5.
4.
6.
Содержание EFFICIENCY PLUS
Страница 1: ...DESIGNER S GUIDE EFFICIENCY BOILER 1 5 0 0 0 0 3 0 0 0 0 0 B T U H R ...
Страница 26: ...28 L o c h i n v a r D E S I G N E R S G U I D E E F F I C I E N C Y B O I L E R 6 1 5 8 8 9 8 9 0 0 Notes ...
Страница 27: ......
Страница 28: ...Lochinvar Corporation 615 889 8900 Fax 615 547 1000 www Lochinvar com EB DG 03 4 5M 2 05 Printed in U S A ...