40
Installation & Service Manual
6
Operation and startup
Maintenance
Listed below are items that must be checked to ensure safe
reliable operations. Verify proper operation after servicing.
CAUTION
Label all wires prior to disconnection
when servicing controls. Wiring erros
can cause improper and dangerous
operation.
1. Examine the venting system at least once a year. Check
more often in first year to determine inspection interval.
Check all joints and pipe connections for tightness,
corrosion or deterioration. Clean screens in the venting
air intake system as required. Have the entire system,
including the venting system, periodically inspected by
a qualified service agency.
2. Using the view port, located below the water
connections, visually check main burner flames at each
start up after long shutdown periods or at least every six
months.
CAUTION
This area is hot and direct contact could
result in burns.
Figure 6-3 Burner Flame Patterns
A. Normal Flame: A normal flame is blue, with
slight yellow tips, with a well defined inner
cone and no flame lifting.
B. Yellow Tip: Yellow tip can be caused by
blockage or partial obstruction of air flow to
the
burner(s).
C. Yellow Flames: Yellow flames can be caused
by blockage of primary air flow to the
burner(s) or excessive gas input. This
condition
MUST
be corrected immediately.
D. Lifting Flames: Lifting flames can be caused
by over firing the burner(s) or excessive
primary
air.
If improper flame is observed, examine the venting system,
ensure proper gas supply and adjust the combustion air.
3. Combustion Air Shutter Adjustment: This appliance uses
a fan assisted combustion process. The fan air shutter is
factory pre-set and should not need adjustment in most
cases. If adjustment is required, the fan air shutter
may be manually adjusted to a dimension specified for
each model. Follow the steps below to adjust the fan air
shutter if the appliance does not function properly or a
continuous low air condition is observed:
COMBUSTION
CHAMBER TOP
AIR SHUTTER
MANOMETER
FAN
TO PRESSURE
SWITCH
BLACK
HOSE
WHITE HOSE
A. Check for proper installation and draft in venting
system. Correct as required.
B. Remove upper front access door.
C. Turn the power switch to the “OFF” position.
D. Turn the gas valve knob to the “OFF” position
E. Use a ruler to measure the distance from the base of the
fan to the end of the air shutter. Compare this distance
to the specified “A” dimension for the appliance.
Figure 6-4 Combustion Air Shutter Adjustment
TABLE 6B
AIR SHUTTER
ADJUSTMENT OPENING
Btu/hr Input
“A” Dimension Output
150,000
1-1/16"
199,999
1-3/16"
250,000
1-5/8"
300,000
1-5/8"