21
9.2
COOLING VENTILATION
When used as a type C appliance, cooling ventilation should be provided as follows:
Model
Input
(Gross)
kW
Input
(Net)
kW
Enclosure/Compartment
Enclosure/Compartment
Internal Space/Boiler Room
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW45-325CE
43.9
39.6
200
200
400
400
N/A
N/A
SHW60-325CE
58.6
52.8
265
265
530
530
N/A
N/A
SHW85-435CE
83.5
75.3
380
380
760
760
152
152
SHW115-435CE
117.2
105.6
530
530
1060
1060
212
212
SHW145-435CE
146.5
132.0
660
660
1320
1320
264
264
TABLE 9.3
COOLING VENTILATION REQUIREMENTS
When used as a type B appliance, provision for cooling ventilation is included in the combustion ventilation
allowance.
10.0
WATER CONNECTIONS
10.1
GENERAL
Recommendations for the water circulation system are given in
BS6644
and
CP 342
. The following notes are of
particular importance.
1.
Circulating pipework not forming part of the useful heating surface should be insulated. Cisterns,
expansion vessels and pipework situated in areas exposed to freezing conditions should also be
insulated.
2.
Drain valves must be located in accessible positions that will permit draining of the entire system
including the unit and any additional storage vessel.
3.
Tapping sizes for connection to the water system are detailed in
Table 3.1 Technical Data
4.
Ideally, individual valves should be fitted to each unit to enable isolation from the system. The
arrangement must comply with the requirements of
BS6644
.
5.
Typical pipework schematics are available from Lochinvar Limited upon request.
10.2
OPEN VENTED SYSTEM ARRANGEMENT
The Lochinvar EcoShield can be used in an open vented arrangement provided that a vent pipe in accordance
with
CP 342
,
BS6644
or
BS6700
as appropriate is fitted. The minimum static head requirement for an open
vented system is 1.0 bar.
10.3
UNVENTED SYSTEM ARRANGEMENT
NOTE:
IT IS STRONGLY RECOMMENDED THAT UNVENTED HOT WATER SYSTEMS BE
INSTALLED BY AN APPROVED INSTALLER.
If the Lochinvar EcoShield is to be used in an unvented arrangement, the system should follow the guidance given
in
BS6700
and must comply with the
Building Regulations 1992: Part G3
. A kit of components that have been
suitably sized for the unvented operation of the appliance is available from Lochinvar Limited. For further
information, contact Lochinvar Limited.
10.3.1
TEMPERATURE AND PRESSURE RELIEF VALVE
A temperature and pressure relief valve is provided in the unvented water system kit. This valve has a lift
pressure of 7 bar and a lift temperature of 90°C. The valve must be fitted to the relief valve tapping located on the
rear of the appliance.
The storage vessel relief valve connection should not be used for any other purpose.