Fit the support bracket around the terminal and secure using appropriate fixings. Do not tighten the
support bracket
8.
Install the remainder of the flue system working progressively away from the water heater supporting the
pipes as necessary.
9.
Once the flue system is fully installed, tighten the clamp to secure the terminal in place.
FIGURE 8.7
VERTICAL TERMINAL ROOF FLASHINGS FOR SYNTHETIC, FLAT AND TILED ROOFS
FIGURE 8.8
INSTALLING TERMINAL THROUGH ROOF FLASHING
8.8.4
TYPE C
43
This appliance can operate on a U-Duct common flue system. The maximum lengths for the interconnecting flue
can be found in
Table 3.1
.
Concrete components of the U-Duct must meet the requirements of
BS EN 1858
Model No.
Mass Rate @ 100%
(@ 9% CO2) (G20)
Mass Rate @ 23%
(@ 9% CO2) (G20)
Mass Rate @ 100%
(@ 10.5% CO2) (G31)
Mass Rate @ 23%
(@ 10.5% CO2) (G31)
SHW45-325CE
16.0
3.7
16.7
3.8
SHW60-325CE
22.3
5.1
23.2
5.3
SHW85-435CE
30.4
7.0
31.6
7.3
SHW115-435CE
42.5
9.8
44.2
10.2
SHW145-435CE
53.2
12.2
55.4
12.7
TABLE 8.4
FLUE GAS MASS RATES