Dual Fuel Supplemental Manual

 WARNING

Do not check for gas leaks with an open 
flame -- use the bubble test.  Failure to 
use the bubble test or check for gas leaks 
can cause severe personal injury, death, or 
substantial property damage.

14.  Turn on the gas supply at the manual gas valve.

15.  Turn the power switch to the “ON” position.

16.  Adjust the temperature set point on the control panel of 
 

the SMART TOUCH control module to the desired 

 

water temperature so the appliance will call for heat.

17.  Check burner performance by cycling the system while 
 

you observe burner response.  The burner should ignite 

 

promptly.  Flame pattern should be stable.  Turn system 

 

off and allow burner to cool, then cycle burner again to 

 

ensure proper ignition and flame characteristics.

18.  Repeat Steps 1 - 17 for both natural and LP gas supply.

Ignition problems are especially noticeable in NEW LP 
installations and also in empty tank situations.  This can 
also occur when a utility company shuts off service to an 
area to provide maintenance to their lines.

Gas valve replacement

The gas valve MUST NOT be replaced with a 
conventional gas valve under any circumstances.  As 
an additional safety feature, the  gas valves have flanged 
connections to the venturis and blowers.

Figure 1-1 Inlet Gas Supply Check_Natural

DO NOT adjust or attempt to 
measure gas valve outlet pressure. 

 

Attempting to alter or measure 
the gas valve outlet pressure could 
result in damage to the valve, 
causing potential severe personal 
injury, death, or substantial property 
damage.

Failure to follow all precautions 
could result in fire, explosion, or 
death!

 WARNING

 WARNING

1  

Gas connections 

(continued)

     

Gas Pressure

The gas pressure must remain between 4 inches w.c. (.99 kPa) 
minimum and 14 inches w.c. (3.5 kPa) maximum for Natural 
gas and between 4 inches w.c. (.99 kPa) minimum and 14 
inches w.c. (3.5 kPa) maximum for LP gas during standby 
(static) mode and while in operating (dynamic) mode.  If an 
in-line regulator is used, it must be a minimum of 10 feet (3 m) 
from the Crest boiler.  It is very important that the gas line is 
properly purged by the gas supplier or utility company.  Failure 
to properly purge the lines or improper line sizing, will result 
in ignition failure.

Figure 1-2 Inlet Gas Supply Check_Propane

IMG00065

Содержание CREST 2.5

Страница 1: ...Crest Installation and Operation Manual and the Crest Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING Save this manual for future reference FBD SUP_100161023_2000004585 Rev D Dual Fuel Supplemental Manual Models FBD 2 5 5 0 ...

Страница 2: ...us situation which if not avoided may result in minor or moderate injury CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BE...

Страница 3: ...ternal to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced When calling or writing about the boiler Please have the boiler model and serial number from the boiler rating plate Consider piping and installation when determining ...

Страница 4: ...s flowing 8 Large natural gas valve Valve 2 Natural The large natural gas valve senses the negative pressure created by the blowers allowing gas to flow only if the gas valves are powered and combustion air is flowing 9 Large propane gas valve Valve 2 Propane The large propane gas valve senses the negative pressure created bytheblowers allowinggastoflowonlyifthegasvalvesarepowered and combustion a...

Страница 5: ...and high altitude Crest Models 4 0 and 5 0 boilers are equipped to operate from 3 000 to 5 500 feet High altitude models are manufactured with different control parameters for high altitude operation but the sequence of operation given in this manual remains the same as the standard boilers A high altitude label as shown in FIG A is also affixed to the unit 6 Standard Crest boilers will de rate by...

Страница 6: ...g to the appliance 13 Remove the manometer from the pressure tap on top of the gas valve Remove the 1 8 3 mm field supplied fitting and reinstall the pipe plug removed in Step 3 DO NOT adjust or attempt to measure gas valve outlet pressure Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve causing potential severe personal injury death or substantial p...

Страница 7: ...es Gas valve replacement The gas valve MUST NOT be replaced with a conventional gas valve under any circumstances As an additional safety feature the gas valves have flanged connections to the venturis and blowers Figure 1 1 Inlet Gas Supply Check_Natural DO NOT adjust or attempt to measure gas valve outlet pressure Attempting to alter or measure the gas valve outlet pressure could result in damag...

Страница 8: ...coming gas pressure less than 4 inches w c 99 kPa If none of the above corrects the problem refer to the Troubleshooting Section of the Crest Service Manual Check system and boiler Check water piping 1 Check system piping for leaks If found shut down the boiler and repair immediately See WARNINGS in the Crest Installation and Operation Manual startup regarding failure to repair leaks 2 Vent any re...

Страница 9: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burn...

Страница 10: ...ice Maintenance Screen place heater into Service Mode by selecting the START button then selecting Set Gas Valve 1 High 6 Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor 7 Once the heat exchanger has modulated up to rate measure the combustion The values should be in the range listed in Table 2A CO levels should be less than 200 ppm for ...

Страница 11: ...on the ball valves for the ones in use 3 total 5 Turn the main power ON 6 Using the Touch Screen accept the appropriate personality identification as shown in FIG 2 4 Figure 2 4 Personality Plug Screen Figure 2 2B Fuel Selector Switch Models 4 0 5 0 IMG00063 NATURAL PROPANE DETAIL MAIN POWER SWITCH NATURAL PERSONALITY I D PROPANE PERSONALITY I D FUEL SELECTION SWITCH IMG00555 ...

Страница 12: ...J3 6 LWCO BOARD J3 3 J3 2 J2 1 J2 2 X6 3 R O K B R O K B R O TEST SWITCH LWCO PROBE R O R O LWCO RESET X6 5 X6 15 BLOWER PROVING SWITCH LARGE R O X6 12 BLOWER PROVING SWITCH SMALL T X13 1 BLOCKED FLUE SWITCH R P X6 6 BLOCKED DRAIN SWITCH K B ENABLE X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 INLET SENSOR OUTLET SENSOR S9 OUTLET SENSOR S1 FLUE SENSOR FLUE SENSOR S10 PRE MIX SENSOR 1 S11 PRE MIX SE...

Страница 13: ...0V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 1 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5...

Страница 14: ...0 5 X10 3 X10 6 X1 6 ON OFF SWITCH GND BK W PR T OR X6 18 X6 8 X1 8 G X6 9 X6 17 X2 4 X13 2 X13 3 BLOWER SMALL BLOWER LARGE R BK GY W W BK T M T GN R W BK W X2 3 X1 7 X1 10 X1 5 FLAME SENSE 2 FLAME SENSE 1 SPARK GENERATOR SPARK ROD X2 5 FLUE DAMPER TRANSFORMER X13 4 FLUE DAMPER 24V TRANSFORMER BL R R R P BK BL Y OR BL Y BK X1 2 X1 3 X1 1 INTEGRATED CONTROL LARGE CONNECTION BOARD SMALL CONNECTION B...

Страница 15: ...0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 18 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 GROUND X6 18 X6 9 ...

Страница 16: ... R O K B R O K B R O TEST SWITCH LWCO PROBE R O R O LWCO RESET X6 5 X6 15 BLOWER PROVING SWITCH LARGE R O X6 12 BLOWER PROVING SWITCH SMALL T X13 1 BLOCKED FLUE SWITCH R P X6 6 BLOCKED DRAIN SWITCH K B ENABLE X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 INLET SENSOR OUTLET SENSOR S9 OUTLET SENSOR S1 FLUE SENSOR FLUE SENSOR S10 PRE MIX SENSOR 1 S11 PRE MIX SENSOR 1 S13 PRE MIX SENSOR 2 S12 PRE MIX ...

Страница 17: ...NSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 18 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 GROUND X6 18 ...

Страница 18: ...Dual Fuel Supplemental Manual Notes 18 ...

Страница 19: ...19 Dual Fuel Supplemental Manual Notes ...

Страница 20: ...ts the update of wiring and ladder diagrams on pages 12 and 13 Revision C ECO C11685 reflects the addition of models 4 0 and 5 0 Revision D Change 500001029 reflects the removal of Models 1 5 and 2 0 along with updates to the control FBD SUP_MM 100161023_DIR 2000004585 Rev D 10 15 ...

Отзывы: