background image

10

        

Dual Fuel Supplemental Manual

2  

Start-up   

Table 2A Flue Products Chart

10.  Repeat the same procedure for propane gas.  Reference the 

Dual Fuel Switching Instructions on pages 10 and 11 of this 
manual.

11. Turn the main power off to the boiler and replace the 

 flue temperature sensor into the flue pipe connection.

12.  Place the boiler back into normal operation.

You must replace the flue gas temperature 
sensor to prevent flue gas spillage into the 
room.  Failure to comply could result in 
severe personal injury, death, or substantial 
property damage.

 WARNING

Gas 

Valve

Natural Gas

Propane

CO

2

O

2

CO

2

O

2

1 - High 3.5% - 5.5% 11.2% - 14.8% 5.1% - 6.8% 10.5% - 13.2%

2 - High 7.8% - 8.6%

5.6% - 7.1%

9.4% - 11.0%

4.1% - 6.6%

Check flame and combustion

1.  Turn the main power off to the boiler by placing 

the “On/Off” switch in the OFF position.

2.  Remove the flue temperature sensor from the flue 

collector.  

Note:

  Combustion measurements will 

be made at this point.

3.  Turn the main power on to the boiler by placing 

the “On/Off” switch in the ON position.

4.  Navigate to the Service Maintenance Screen from 

the Home Screen by pressing the SETUP button, 
enter the installer password, and then using the 
scrolling menu feature on the left side, scroll down 
to the SERVICE MAINTENANCE button.      

5.  On the Service Maintenance Screen place heater 

into Service Mode by selecting the START button, 
then selecting 

Set Gas Valve 1 - High

.  

6.  Insert the probe from a combustion analyzer into 

the hole left by the removal of the flue temperature 
sensor.

7.  Once the heat exchanger has modulated up to 

rate, measure the combustion.  The values should 
be in the range listed in Table 2A.  CO levels 
should be less than 200 ppm for a properly 
installed unit.  If the combustion is not within 
range reference the 

Troubleshooting

 Section in 

the Crest Service Manual for possible causes and 
corrective actions.   

 

 NOTICE

A flame and combustion check 
must be performed on natural gas 
and then repeated on propane.

8. After 

Gas Valve 1

 is set, repeat the same procedure for the second 

gas train by selecting 

Set Gas Valve 2 - High

 on the Service 

Screen.

9.   Once the heater analysis is complete, test the safety shutoff device 

by turning the manual shutoff valve to the OFF position and 
ensuring that the heater shuts down and registers an alarm.  Open 
the manual shutoff valve and reset the control. 

Dual fuel switching instructions

1.  Turn the main power off to the boiler by placing the 

“On/Off” switch in the OFF position (FIG.’s 2-2A and 
2-2B).

2.  Using the fuel selector switch (FIG.’s 2-2A and 2-2B), 

select the desired fuel.

Figure 2-2A Fuel Selector Switch - Models 2.5 - 3.5

IMG00063

NATURAL

PROPANE

DETAIL

IMG00064

MAIN POWER
SWITCH

NATURAL PERSONALITY I.D.

PROPANE PERSONALITY I.D.

FUEL SELECTION

SWITCH

Содержание CREST 2.5

Страница 1: ...Crest Installation and Operation Manual and the Crest Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING Save this manual for future reference FBD SUP_100161023_2000004585 Rev D Dual Fuel Supplemental Manual Models FBD 2 5 5 0 ...

Страница 2: ...us situation which if not avoided may result in minor or moderate injury CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BE...

Страница 3: ...ternal to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced When calling or writing about the boiler Please have the boiler model and serial number from the boiler rating plate Consider piping and installation when determining ...

Страница 4: ...s flowing 8 Large natural gas valve Valve 2 Natural The large natural gas valve senses the negative pressure created by the blowers allowing gas to flow only if the gas valves are powered and combustion air is flowing 9 Large propane gas valve Valve 2 Propane The large propane gas valve senses the negative pressure created bytheblowers allowinggastoflowonlyifthegasvalvesarepowered and combustion a...

Страница 5: ...and high altitude Crest Models 4 0 and 5 0 boilers are equipped to operate from 3 000 to 5 500 feet High altitude models are manufactured with different control parameters for high altitude operation but the sequence of operation given in this manual remains the same as the standard boilers A high altitude label as shown in FIG A is also affixed to the unit 6 Standard Crest boilers will de rate by...

Страница 6: ...g to the appliance 13 Remove the manometer from the pressure tap on top of the gas valve Remove the 1 8 3 mm field supplied fitting and reinstall the pipe plug removed in Step 3 DO NOT adjust or attempt to measure gas valve outlet pressure Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve causing potential severe personal injury death or substantial p...

Страница 7: ...es Gas valve replacement The gas valve MUST NOT be replaced with a conventional gas valve under any circumstances As an additional safety feature the gas valves have flanged connections to the venturis and blowers Figure 1 1 Inlet Gas Supply Check_Natural DO NOT adjust or attempt to measure gas valve outlet pressure Attempting to alter or measure the gas valve outlet pressure could result in damag...

Страница 8: ...coming gas pressure less than 4 inches w c 99 kPa If none of the above corrects the problem refer to the Troubleshooting Section of the Crest Service Manual Check system and boiler Check water piping 1 Check system piping for leaks If found shut down the boiler and repair immediately See WARNINGS in the Crest Installation and Operation Manual startup regarding failure to repair leaks 2 Vent any re...

Страница 9: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burn...

Страница 10: ...ice Maintenance Screen place heater into Service Mode by selecting the START button then selecting Set Gas Valve 1 High 6 Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor 7 Once the heat exchanger has modulated up to rate measure the combustion The values should be in the range listed in Table 2A CO levels should be less than 200 ppm for ...

Страница 11: ...on the ball valves for the ones in use 3 total 5 Turn the main power ON 6 Using the Touch Screen accept the appropriate personality identification as shown in FIG 2 4 Figure 2 4 Personality Plug Screen Figure 2 2B Fuel Selector Switch Models 4 0 5 0 IMG00063 NATURAL PROPANE DETAIL MAIN POWER SWITCH NATURAL PERSONALITY I D PROPANE PERSONALITY I D FUEL SELECTION SWITCH IMG00555 ...

Страница 12: ...J3 6 LWCO BOARD J3 3 J3 2 J2 1 J2 2 X6 3 R O K B R O K B R O TEST SWITCH LWCO PROBE R O R O LWCO RESET X6 5 X6 15 BLOWER PROVING SWITCH LARGE R O X6 12 BLOWER PROVING SWITCH SMALL T X13 1 BLOCKED FLUE SWITCH R P X6 6 BLOCKED DRAIN SWITCH K B ENABLE X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 INLET SENSOR OUTLET SENSOR S9 OUTLET SENSOR S1 FLUE SENSOR FLUE SENSOR S10 PRE MIX SENSOR 1 S11 PRE MIX SE...

Страница 13: ...0V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 1 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5...

Страница 14: ...0 5 X10 3 X10 6 X1 6 ON OFF SWITCH GND BK W PR T OR X6 18 X6 8 X1 8 G X6 9 X6 17 X2 4 X13 2 X13 3 BLOWER SMALL BLOWER LARGE R BK GY W W BK T M T GN R W BK W X2 3 X1 7 X1 10 X1 5 FLAME SENSE 2 FLAME SENSE 1 SPARK GENERATOR SPARK ROD X2 5 FLUE DAMPER TRANSFORMER X13 4 FLUE DAMPER 24V TRANSFORMER BL R R R P BK BL Y OR BL Y BK X1 2 X1 3 X1 1 INTEGRATED CONTROL LARGE CONNECTION BOARD SMALL CONNECTION B...

Страница 15: ...0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 18 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 GROUND X6 18 X6 9 ...

Страница 16: ... R O K B R O K B R O TEST SWITCH LWCO PROBE R O R O LWCO RESET X6 5 X6 15 BLOWER PROVING SWITCH LARGE R O X6 12 BLOWER PROVING SWITCH SMALL T X13 1 BLOCKED FLUE SWITCH R P X6 6 BLOCKED DRAIN SWITCH K B ENABLE X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 INLET SENSOR OUTLET SENSOR S9 OUTLET SENSOR S1 FLUE SENSOR FLUE SENSOR S10 PRE MIX SENSOR 1 S11 PRE MIX SENSOR 1 S13 PRE MIX SENSOR 2 S12 PRE MIX ...

Страница 17: ...NSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 BAS X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL X8 5 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 18 T INLET SENSOR X8 3 X8 8 X8 2 X8 4 X8 9 X7 1 X7 5 X7 2 X7 6 GROUND X6 18 ...

Страница 18: ...Dual Fuel Supplemental Manual Notes 18 ...

Страница 19: ...19 Dual Fuel Supplemental Manual Notes ...

Страница 20: ...ts the update of wiring and ladder diagrams on pages 12 and 13 Revision C ECO C11685 reflects the addition of models 4 0 and 5 0 Revision D Change 500001029 reflects the removal of Models 1 5 and 2 0 along with updates to the control FBD SUP_MM 100161023_DIR 2000004585 Rev D 10 15 ...

Отзывы: