15

provide combustion, ventilation and dilution air.

Unusually Tight Construction

In unconfined spaces in buildings, infiltration may be adequate 
to  provide  air  for  combustion,  ventilation  and  dilution  of  flue 
gases. However, in buildings of unusually tight construction (for 
example,  weather  stripping,  heavily  insulated,  caulked,  vapor 
barrier, etc.) additional air must be provided using the methods 
described in the Confined Space section that follows.

CONFINED SPACE

A Confined Space is one whose volume IS LESS THAN 50 cubic 

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 

rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, 

ventilation and dilution in confined spaces. The required size for 

the openings is dependent on the method used to provide fresh 

air to the confined space AND the total Btu/hr input rating of all 

appliances installed in the space.

Exhaust Fans

Where exhaust fans are installed, additional air shall be provided 

to replace the exhausted air. When an exhaust fan is installed 

in  the  same  space  with  a  water  heater,  sufficient  openings  to 

provide  fresh  air  must  be  provided  that  accommodate  the 

requirements for all appliances in the room and the exhaust fan. 

Undersized openings will cause air to be drawn into the room 

through the water heater’s vent system causing poor combustion. 

Sooting, serious damage to the water heater and the risk of fire 

or explosion may result. It can also create a risk of asphyxiation.

Louvers and Grilles

The free areas of the fresh air openings in the instructions that 

follow do not take in to account the presence of louvers, grilles or 

screens in the openings.
The  required  size  of  openings  for  combustion,  ventilation  and 

dilution air shall be based on the “net free area” of each opening. 

Where the free area through a design of louver or grille or screen 

is  known,  it  shall  be  used  in  calculating  the  size  of  opening 

required to provide the free area specified. Where the louver and 

grille design and free area are not known, it shall be assumed 

that wood louvers will have 25% free area and metal louvers and 

grilles will have 75% free area. Non motorized louvers and grilles 

shall be fixed in the open position.

AIR REQUIREMENTS

Breathing Hazard - Carbon Monoxide Gas

Install water heater in accordance with

the Instruction Manual and NFPA 54 or

CAN/CSA-B149.1.
To avoid injury, combustion and ventilation

air must be taken from outdoors.
Do not place chemical vapor  emitting

products near water heater.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

For safe operation an adequate supply of fresh uncontaminated 

air for combustion and ventilation must be provided.
An insufficient supply of air can cause recirculation of combustion 

products  resulting  in  contamination  that  may  be  hazardous  to 

life. Such a condition often will result in a yellow, luminous burner 

flame, causing sooting of the combustion chamber, burners and 

flue tubes and creates a risk of asphyxiation.
Do  not  install  the  water  heater  in  a  confined  space  unless  an 

adequate supply of air for combustion and ventilation is brought 

in  to  that  space  using  the  methods  described  in  the  Confined 

Space section that follows.
Never obstruct the flow of ventilation air. If you have any doubts 

or questions at all, call your gas supplier. Failure to provide the 

proper amount of combustion air can result in a fire or explosion 

and cause property damage, serious bodily injury or death.

UNCONFINED SPACE

An Unconfined Space is one whose volume IS NOT LESS THAN 

50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the 

total input rating of all appliances installed in the space. Rooms 

communicating directly with the space, in which the appliances 

are  installed,  through  openings  not  furnished  with  doors,  are 

considered a part of the unconfined space.
Makeup  air  requirements  for  the  operation  of  exhaust  fans, 

kitchen ventilation systems, clothes dryers and fireplaces shall 

also be considered in determining the adequacy of a space to 

Содержание CLN 120080

Страница 1: ...her appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor...

Страница 2: ...51 TABLE OF CONTENTS SAFE INSTALLATION USE AND SERVICE 3 APPROVALS 3 GENERAL SAFETY INFORMATION 4 Precautions 5 Grounding Instructions 5 Hydrogen Gas Flammable 5 INTRODUCTION 6 Abbreviations Used 6 Q...

Страница 3: ...of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances WARNING This product contains a chemical known to the St...

Страница 4: ...nce with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service technician for...

Страница 5: ...ot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCE...

Страница 6: ...ything on the first few pages RE AD THE ENTIRE MANUAL BE FORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER 2 The installation must conform with these instructions and the local code authority hav...

Страница 7: ...of high limit switch operation the water heater cannot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the control then ne...

Страница 8: ...307 LPH 1818 1636 1309 1212 1091 935 909 818 727 654 606 595 545 519 503 467 CLN199080 199 81 80 GPH 531 478 382 354 319 273 265 239 212 191 177 174 159 152 147 137 58 307 LPH 2009 1808 1447 1340 120...

Страница 9: ...he panel must be strong enough to carry the weight of the heater when full of water A service clearance of at least 24 61 cm should be maintained from serviceable parts TABLE 4 MINIMUM CLEARANCES TO C...

Страница 10: ...instruction labels from the manufacturer for placement on the blanket directly over the existing labels DO inspect the insulation blanket frequently to make certain it does not sag thereby obstructing...

Страница 11: ...me circulating pumps are manufactured with sealed bearings and do not require further lubrication Some circulating pumps must be periodically oiled Refer to the pump manufacturer s instructions for lu...

Страница 12: ...with all gas burning equipment running at maximum rate dynamic pressure The gas supply pressure must be stable within 1 5 W C 0 37 kPa from static to dynamic pressure to provide good performance Press...

Страница 13: ...1 and Water Piping Diagrams starting on page 35 TEMPERATURE PRESSURE RELIEF VALVE Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized t...

Страница 14: ...ve is not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems an...

Страница 15: ...ening required to provide the free area specified Where the louver and grille design and free area are not known it shall be assumed that wood louvers will have 25 free area and metal louvers and gril...

Страница 16: ...hes 300 mm of the top of the enclosure shall be provided See Figure 14 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches l50 mm from the front of the...

Страница 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 OUTDOOR AIR THROUGH TWO VERTICAL DUCTS The illustrations shown in thi...

Страница 18: ...Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system is exposed to ambient temperatures below 40 F 4 4 C it must be insulated to prevent condensation Do not...

Страница 19: ...sands of Btu hr Manifold and Common Vent Diameter Inches 2 308 000 7 7 6 6 6 6 6 6 3 462 000 8 8 7 7 7 6 6 6 4 616 000 9 9 9 8 8 7 7 6 Model CLN180080 THRU 199100 Input 180 000 and 199 000 Btu hr Tota...

Страница 20: ...8 8 7 7 7 6 6 Number of Heaters Combined Input Btu hr 2 620 000 12 10 10 9 9 8 8 7 3 930 000 14 14 12 12 10 10 9 9 4 1 240 000 16 14 14 14 12 12 10 9 Model CLN366085 Input 366 000 btu hr Total Vent He...

Страница 21: ...installation of the water piping begins 1 Water Temperature Control and Mixing Valves on page 12 2 Dishwashing Machines on page 13 3 Temperature Pressure Relief Valve on page 13 4 Closed Systems and T...

Страница 22: ...inlet water connection requires an inlet dip tube refer to figure 19 The tube is supplied in the heater Follow caution labels if applying heat to this fitting Do not allow pipe dope to contact the pla...

Страница 23: ...sing In this case 200 C rated wire must be used The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neutral connections 24V 24V GND GND PV MV PV MV SPARK 4...

Страница 24: ...e Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping see Figu...

Страница 25: ...from faucets after extended periods of non use 1 Close the Main Gas Shutoff Valve see Figure 21 on page 24 2 Purge all air from the supply gas line up to the water heater s Main Gas Shutoff Valve 3 W...

Страница 26: ...pply gas regulator as necessary Adjust the supply gas regulator s per the regulator manufacturer s instructions to achieve the required static and dynamic supply gas pressure Multiple Water Heater Ins...

Страница 27: ...n off the 24vac power to the blower relay and the Ignition Control and the unit will be in standby mode until another call for heat is initiated by the thermostat See the flow chart on page 28 for mor...

Страница 28: ...NO Blower power relay is energized to start blower Igni onControlprovidespowertoSpark IgniterandPilotGasValveandmonitors FlameSensortodetermineifBurnerislit 24VAC power to the Igni on Control and self...

Страница 29: ...thermal expansion in a closed system See Closed Water Systems and Thermal Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temper...

Страница 30: ...this manual 11 Turn on the electrical supply to place the water heater back in operation 12 Turn on the gas supply to the water heater at the Main Gas Shutoff Valve 13 Allow the water heater to compl...

Страница 31: ...ut opening and scrape out any loose deposits of scale or sediment This is an economical way to avoid unnecessary usage of the deliming solution Repeat the opening and closing of the cold water inlet v...

Страница 32: ...plying Teflon tape or paste to threads Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection Do not over tighten to avoid damage to threads and fittings Prepare the...

Страница 33: ...ot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the thermostat then needs to be depressed See Figure 2 for the location...

Страница 34: ...blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment accumulation on bottom of tank Drain a quantity of water...

Страница 35: ...should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Страница 36: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Страница 37: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Страница 38: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Страница 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 40: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 41: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Страница 42: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Страница 43: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Страница 44: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Страница 45: ...an the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT B...

Страница 46: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PO...

Страница 47: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Страница 48: ...perature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPE...

Страница 49: ...emperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE T...

Страница 50: ...NOTES 50...

Страница 51: ...51 NOTES...

Страница 52: ...300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com Copyright 2014 Lochinvar LLC All rights reserved...

Отзывы: