Instruction manual CHA
49
gis
9
Starting the water
heater
9.1
Introduction
Topics covered in this chapter, in sequence:
•
Starting the appliance
.
•
The appliance's heating cycle
.
9.2
Starting the appliance
Start the water heater as follows:
1. Fill the water heater
(5 "Filling")
.
2. Open
(3.5 "Installation diagram")
the manual gas
valve.
3. Switch on the power to the water heater using the
isolator between the water heater and the power
supply.
4. Use the ON/OFF switch on the control panel to put
the appliance in 'ON' mode (position 'I') or the
weekly program mode (position 'II'); see paragraph
6.2 'Operating modes'.
5. Set the desired water temperature using the
control thermostat
(7.5 "Control thermostat")
.
If there is a heat demand, the appliance will run
through the heating cycle
(9.3 "The appliance's
heating cycle")
.
9.3
The appliance's heating cycle
The appliance's heating cycle is activated when the
measured water temperature (T
water
) falls below the
threshold value (T
set
). This threshold value depends
on the currently selected appliance operating mode. If
the appliance is in the 'OFF' mode (frost protection),
for example, this value is 20°C. If the appliance is in
the 'ON' mode, this threshold value can be selected,
for example, position 3 (±60°C).
The heating cycle runs successively through the
following states:
1. HEAT DEMAND;
2. WAITING TIME;
3. PRE-GLOW;
4. IGNITION;
5. RUNNING;
6. WAITING TIME.
The complete cycle is explained in the example set out
below.
Comment
The appliance runs through an identical cycle
when frost protection is activated.
1. The control thermostat sensor measures the water
temperature. The water temperature falls below
the set temperature of (for example) 60°C, causing
the control thermostat to close. The burner control
now detects a demand and starts the heating
cycle.
2. Following demand, the waiting time starts. This
waiting time ensures that ignition takes place
safely. The waiting time lasts about 15 seconds.
3. Once the waiting time is over (audible 'clicking' of
the relay in the burner control) the pre-glowing of
the hot surface igniter is started
4. After about 12 seconds (pre-)glowing, the gas
control is opened and ignition can take place.
5. After ignition, the flame is detected and the
appliance will be running. This means that actual
heating has started.
6. When the water reaches the set temperature, the
demand ceases. The gas control closes, and the
burner tray is extinguished. A new waiting time
begins, of about 10 seconds.
7. After this waiting time, the appliance enters an idle
state, and waits until the water temperature again
falls below the set temperature.
With any subsequent heat demand, the heating cycle
will resume from step 1.
Содержание CHA 100 CE
Страница 4: ...4 Instruction manual CHA gis...
Страница 10: ...Introduction 10 Instruction manual CHA 1 gis...
Страница 32: ...Installation 32 Instruction manual CHA 3 is...
Страница 40: ...Conversion to a different gas category 40 Instruction manual CHA 4 is...
Страница 50: ...Starting the water heater 50 Instruction manual CHA 9 gis...
Страница 52: ...Shutting down 52 Instruction manual CHA 10 gis...
Страница 70: ...Electrical diagram 70 Instruction manual CHA 14 is...
Страница 72: ...Declaration of Conformity 72 Instruction manual CHA 15 is...
Страница 74: ...0310 569 1 0 UK Index Instruction manual CHA...