11
ModBus and BACnet Instructions
5
BACnet Memory Map
Primary Data Tables
Object Type
Data Type
Read / Write
Binary Input (BI)
Single Bit
Read Only
Binary Value (BV)
Single Bit
Read / Write
Analog Input (AI)
16-Bit Word
Read Only
Analog Value (AV)
16 Bit Word
Read / Write
Memory Map
Object Name
Object
Type
Object
Instance
Units
Min
Max
Resolution
Binary Values
Enable
BV
0
none
0
1
1
Tank Thermostat
BV
4
none
0
1
1
Binary Inputs
Manual Reset High Limit
BI
0
none
0
1
1
Flow Switch
BI
1
none
0
1
1
Gas Pressure Switch
BI
2
none
0
1
1
Louver Proving Switch
BI
3
none
0
1
1
Blocked Drain Switch
BI
5
none
0
1
1
Auto Reset High Limit
BI
6
none
0
1
1
Flame
BI
7
none
0
1
1
Enable
BI
8
none
0
1
1
Tank Thermostat
BI
9
none
0
1
1
Run Time Contacts
BI
32
none
0
1
1
Alarm Contacts
BI
33
none
0
1
1
DHW Pump
BI
35
none
0
1
1
Gas Valve
BI
37
none
0
1
1
Recirculation Pump
BI
38
none
0
1
1
Power Fan
BI
48
none
0
1
1