background image

23

Nominal

Iron Pipe

Size (Inches)

Single Unit

Natural Gas Pipe Capacity Chart

Length of Pipe in Straight Feet for 1/2 PSI

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1/2

175

120

97

82

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1

697

477

384

328

292

267

246

236

210

200

179

164

149

138

1-1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

1-1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

2

4100

2820

2260

1950

1720

1560

1440

1330

1250

1180

1100

974

871

820

2-1/2

6460

4460

3610

3100

2720

2460

2310

2100

2000

1900

1700

1540

1400

1300

3

11200

7900

6400

5400

4870

4410

4000

3800

3540

3330

3000

2720

2500

2340

4

23500

16100 13100 11100 10000

9000

8300

7690

7380

6870

6150

5640

5130

4720

Outdoor Armor water heaters are typically shipped ready to fire on natural gas.  Check the water heater rating 
plate to determine which fuel the water heater is set for.  If set to natural gas, it may be converted to LP by 
installing an orifice or by making a gas valve adjustment (see pages 11 and 12).  In order to operate on LP gas, 
an orifice MUST BE installed or a gas valve adjustment MUST BE made.  Failure to comply could result in severe 
personal injury, death, or substantial property damage.

Table 4A Natural Gas Pipe Size Chart

The gas piping must be sized for the proper flow and length of 
pipe, to avoid excessive pressure drop.  Both the gas meter and 
the gas regulator must be properly sized for the total gas load.  

If you experience a pressure drop greater than 1 inch w.c., the 
meter, regulator, or gas line is undersized or in need of service.  
Perform the steps below when checking inlet gas supply:

1.  Turn the main power switch to the “OFF” position.

2.  Shut off gas supply at the manual gas valve in the gas 
 

piping to the appliance.  

3.  On Models 151 - 501 loosen the set screw one (1) full 
 

turn from inside the pressure tap on top of the gas valve.  

 

On Models 601 - 801 remove the 1/8" (3 mm) pipe plug 

 

on the inlet flange to the valve and install a suitable 1/8" 

 

(3 mm) fitting (field supplied) for the manometer tubing.  

 

Place the tubing of the manometer over the tap once the 

 

set screw is loosened or the 1/8" (3 mm) fitting is installed 

 

(depending on model) as shown in FIG.’s 4-6 thru 4-9 on 

 page 

24.

4.  Slowly turn on the gas supply at the field installed 
 

manual gas valve.

 WARNING

5.  Turn the power switch to the “ON” position.
6.  Adjust the temperature set point on the control panel of 
 

the SMART SYSTEM control module to call for heat.

7.  Observe the gas supply pressure as the burner fires at 
 

100% of rated input.  Percent of burner input will be 

 

displayed on the control panel.

8.  Ensure inlet pressure is within specified range. 

 

 

Minimum and maximum gas supply pressures are 

 

specified in this section of the manual.

9.  If gas supply pressure is within normal range and no 
 

adjustments are needed, proceed on to Step 11.  

10.  If the gas pressure is out of range, contact the gas utility, 
 

gas supplier, qualified installer or service agency to 

 

determine the necessary steps to provide proper gas 

 

pressure to the control.

11.  Turn the power switch to the “OFF” position.
12.  Shut off the gas supply at the manual gas valve in the gas 
 

piping to the appliance.  

13.  Remove the manometer from the pressure tap on top of 
 

the gas valve.  On Models 151 - 501 re-tighten the set 

 

screw inside the pressure tap.   On Models 601 - 801 

 

remove the 1/8" (3 mm) field supplied fitting and 

 

reinstall the pipe plug removed in Step 3.

Check inlet gas supply

 NOTICE

CSA or UL listed flexible gas connections are 
acceptable, but you must exercise caution to 
ensure that the line has adequate capacity 
to allow your water heater to fire at full 
rate.  Consult with local codes for proper 
installation or service procedures.

DO NOT adjust or attempt to measure 
gas valve outlet pressure.  The gas valve is 
factory-set for the correct outlet pressure.  
This setting is suitable for natural gas and 
propane, requiring no field adjustment. 

 

Attempting to alter or measure the gas valve 
outlet pressure could result in damage to 
the valve, causing potential severe personal 
injury, death, or substantial property damage.

 WARNING

4  

Gas connections 

(continued)

  

 WARNING

When re-tightening the set screw, be sure to 
tighten securely to prevent gas leaks.

Do not check for gas leaks with an open 
flame -- use the bubble test.  Failure to 
use the bubble test or check for gas leaks 
can cause severe personal injury, death, or 
substantial property damage.

14.  Turn on the gas supply at the manual gas valve.

15.  Turn the power switch to the “ON” position.

16.  Adjust the temperature set point on the control panel of 
 

the SMART SYSTEM control module to the desired 

 

water temperature so the appliance will call for heat.

   Outdoor Armor Water Heater 

Installation & Operation Manual

Содержание 151 - 801

Страница 1: ...is water heater MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electri...

Страница 2: ...ERMINE WATER HEATER LOCATION Provide Clearances 9 Outdoor Vent Air Intake Location 9 Flooring and Foundation 9 Prevent Combustion Air Contamination 9 Corrosive Contaminants and Sources 9 2 PREPARE WAT...

Страница 3: ...ter if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced When calli...

Страница 4: ...points for the line voltage power and the pump 18 Water heater drain port Location from which the heat exchanger can be drained 19 Low voltage connection board The connection board is used to connect...

Страница 5: ...360 26 31 40 15 19 24 1 Left Side inside unit Model 286 The Outdoor Armor Water Heater How it works continued Left Side inside unit Models 151 200 Models 151 200 19 10 16 23 28 21 32 18 7 12 27 13 8 4...

Страница 6: ...42 20 39 27 14 IMG00395 Models 400 501 2 28 16 23 3 5 34 15 17 4 8 7 18 32 21 26 IMG00396 19 1 Rear View Models 400 501 Left Side inside unit Models 400 501 41 27 9 12 13 39 42 25 14 20 29 IMG00288 30...

Страница 7: ...he outdoor water heater is listed to UL353 The auto reset high limit is listed to ANSI Z21 87 7 Maximum allowed working pressure is located on the rating plate NOTICE Model Number Note Change N to L f...

Страница 8: ...ocate unit at least 3 feet 0 91m from any wall or vertical surface to prevent wind conditions from affecting performance The outdoor unit must not be installed in an area that is enclosed by walls or...

Страница 9: ...hich may cause contaminated combustion air Outdoor vent air intake location The flue products discharged from the flue outlet on the outdoor vent may be very hot Avoid touching or other direct contact...

Страница 10: ...REWS WALL STRAP ELBOW FLUE PIPE VENT TERMINATION VENT COVER CLAMP IMG00445 NOTE VERIFY GASKETS ARE SEATED EVENLY INSIDE THE GROOVE Figure 2 3 Install Flue Pipe Assembly Models 701 801 5 Slide the flue...

Страница 11: ...ice Models 151 286 Models 151 286 1 Remove the top and front access covers from the unit Phillips screwdriver required for removal 2 Remove the three screws securing the gas valve to the venturi FIG 2...

Страница 12: ...vel a Adjust legs if necessary to level the water heater see FIG 2 8 below COVER ALLEN WRENCH ADJUSTMENT SCREW Figure 2 7 Gas Valve Adjustment Models 601 801 Models 601 801 1 Remove the top access cov...

Страница 13: ...ng required by local codes NOTICE Flow switch and relief valve installation Basic steps are listed below to guide you through the installation of the flow switch and relief valve provided with the uni...

Страница 14: ...he amount of turns listed in Table 3A based on the model Consult the manufacturer s instructions for wiring the flow switch to your system NOTICE Be sure to install flow switch so that the arrow on th...

Страница 15: ...to achieve proper operation As shipped from the factory the tank sensor is in the literature package shipped with the unit Placing the sensor in the tapping provided on the storage tank will improve t...

Страница 16: ...o support the weight of the water heater circulator pump with the piping or its accessories Refer to the pump manufacturer s installation instructions Failure to comply could result in severe personal...

Страница 17: ...mp with the piping or its accessories Refer to the pump manufacturer s installation instructions Failure to comply could result in severe personal injury death or substantial property damage CAUTION F...

Страница 18: ...e illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes Indoor tank shown for illustration purposes The piping...

Страница 19: ...4 5 5 501 3 3 1 2 4 5 5 5 6 601 3 3 1 2 4 5 5 5 6 701 3 4 5 5 6 6 6 801 3 4 5 6 6 6 6 NOTICE Please note that these illustrations are meant to show system piping concept only the installer is responsi...

Страница 20: ...etailing required by local codes Indoor tank shown for illustration purposes Model Number of Units 2 3 4 5 6 7 8 Required Pipe Sizes in NPT 151 1 1 2 2 2 2 2 1 2 3 3 200 1 1 2 2 2 1 2 2 1 2 3 3 4 286...

Страница 21: ...e appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1 2 PSIG 3 5 kPa b The appliance must be isolated from the...

Страница 22: ...wing verify during water heater startup 2 Install 100 lockup gas pressure regulator in supply line if inlet pressure can exceed 14 inches w c at any time Adjust lockup regulator for 14 inches w c maxi...

Страница 23: ...on the gas supply at the field installed manual gas valve WARNING 5 Turn the power switch to the ON position 6 Adjust the temperature set point on the control panel of the SMART SYSTEM control module...

Страница 24: ...PLACE THE MANOMETER TUBING OVER THE PRESSURE TAP Figure 4 8 Inlet Gas Supply Check Model 501 DO NOT adjust gas valve outlet pressure The gas valve is factory set for the correct outlet pressure This...

Страница 25: ...ter pump is shipped loose on all Armor models Wire the water heater pump as shown in FIG 5 1 4 The outdoor water heater is capable of controlling a building recirculation pump field supplied Wire the...

Страница 26: ...pair cable If desired the shield can be connected to ground by installing a jumper wire between terminals 1 and 3 on connector X5 on the optional ModBus interface module NOTICE See Section 4 Gas Conn...

Страница 27: ...hould be wired to the low voltage connection board at the terminals marked for the tank sensor see FIG 5 3 The Leader control will use the water temperature at the tank sensor to control the operation...

Страница 28: ...BUILDING MANAGEMENT SYSTEM COM NO LOW WATER CUTOFF TANK THERMOSTAT SHIELD SHIELD TO NEXT HEATER A B A B FROM PREVIOUS HEATER A B IMG00423 Figure 5 3 Low Voltage Field Wiring Connections Outdoor Armor...

Страница 29: ...proved by the authority having jurisdiction In the absence of other authority PVC and CPVC pipe must comply with ASTM D1785 or D2845 Cement and primer must comply with ASME D2564 or F493 8 A condensat...

Страница 30: ...ersonal injury death or substantial property damage PVC TEE ASSEMBLY FACTORY SUPPLIED TO FLOOR DRAIN 2 PVC CAP WITH BLOCKED DRAIN SWITCH RETAINING SCREW CONDENSATE FROM HEAT EXCHANGER Figure 7 1 Conde...

Страница 31: ...Check for gastight seal at every connection seam of air piping and vent piping Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions which will result in s...

Страница 32: ...all a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety i...

Страница 33: ...33 7 Start up continued Figure 7 3 Operating Instructions Models 400 801 Outdoor Armor Water Heater Installation Operation Manual...

Страница 34: ...ition and ensuring that the water heater shuts down and registers an alarm Open the manual shutoff valve and reset the control 9 Turn the main power off to the water heater 10 Place the water heater b...

Страница 35: ...en status NOTICE Please note that the brackets denote screen status NOTICE When installed in a Cascade system the individual controls must be programmed for cascade operation This is accomplished by a...

Страница 36: ...outlet temperature sensor When the outlet temperature exceeds 185 F the unit will reduce the fan speed If the outlet water temperature exceeds 195 F the control will shut the unit down until it cools...

Страница 37: ...continued 1 Turn ON the main power to the water heater by placing the ON OFF switch in the ON position 2 From the Status Screen press the NAVIGATION dial to access the Set Points Screen 3 Press the L...

Страница 38: ...page 34 of this manual to program the set point If the water temperature at the tank is less than the set point differential then the control will initiate a call for heat on the Cascade see the Outd...

Страница 39: ...larger models the control will lock out if this second attempt also fails On the 400 and smaller models the control will perform a total of 4 attempts before locking out 6 If flame is detected it hold...

Страница 40: ...and monitor water heater operation 8 Operating information The information on the bottom of the display shows the functions of the two SELECT keys on either corner and the NAVIGATION dial in the cente...

Страница 41: ...ing at the displayed percentage POSTPURGE The call for heat has been satisfied and the unit runs the fan for an additional 10 seconds to clear the combustion chamber and vent system of residual flue p...

Страница 42: ...UMP The status of the DHW pump output BMS VOLTAGE The voltage received from a BMS system RATE OUTPUT A 0 10V signal indicating the firing rate of the water heater DHW RUN HOURS The total hours of oper...

Страница 43: ...ION dial will display the Set Points Screen Turning the NAVIGATION dial will move the cursor up or down Turning the NAVIGATION dial will increase or decrease the current setting F RIGHT SELECT key fun...

Страница 44: ...kout and performance verification per Section 7 of this manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than...

Страница 45: ...and inspect the interior of the water heater 2 Vacuum any sediment from inside the water heater and components Remove any obstructions Clean condensate trap 1 Inspect the condensate drain line condens...

Страница 46: ...ere personal injury death or substantial property damage Following installation the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear Certain naturally occurring min...

Страница 47: ...eaning heat exchanger For recommended materials including brush appropriate extension s refractory cover and detailed instructions see Table 9B Heat Exchanger Cleaning Kits 1 Shut down water heater Fo...

Страница 48: ...n 4 Wheel Brush MSC20084 3mm Allen Wrench MSC20086 1 4 x 24 Drill Extension 501 801 KIT30064 CTN20005 Rear Refractory Cover MSC20083 Nylon 4 Wheel Brush MSC20085 1 4 x 12 Drill Extension MSC20086 1 4...

Страница 49: ...water or electricity connected to the unit As such actual switch states may vary from those shown on diagrams depending upon whether utilities are connected or a fault condition is present 2 See wiri...

Страница 50: ...st be replaced with wire having same wire gauge AWG and rated for a minimum of 105 C Exceptions Replacement high voltage spark lead and ribbon cables must be purchased from the factory Use of a non ap...

Страница 51: ...Notes Installation Operation Manual OUTDOOR CONDENSING WATER HEATER 51...

Страница 52: ...C12102 reflects the addition of condensate kit option information for areas that may reach below 32 F as well as a warning not to install OA 400 in these areas and Table 1A on page 8 Revision D ECO C1...

Отзывы: