TO SET FULL SCALE

ï After hook-up, f ind your HP , KW or % fr om the chart.

ï Decide if y ou want to display HP, % or KW .

ï The

 c ycles through the choices sho wn below and

blinks slowly for each choice. Each pr ess of 

 moves

you to the next choice.

FULL

SCALE

FULL

SCALE

FRONT P ANEL SET-UP TIPS

1) None of t he settings will be changed until you hold

down 

and the fast blinking stops.

2) Five seconds af ter you have pressed a button, the

Control will return to normal oper ation.

3) If you hold do wn the 

digits will continue to

change.

4) You only need t o do 

when you install the Contr ol

(or if y ou change the hook-up).

ENTER

FULL

SCALE

DIGITS

Æ

DECIMAL

Æ

DECIMAL

Æ

DECIMAL

Æ

HP

Æ

%

Æ

KW

XXX.

XX.X

X.XX

   to change

if this is

if this is

if this is

if this is

if this is

if this is

your choice,

your choice,

your choice,

your choice,

your choice,

your choice,

press

press

press

press

press

press

 

Ø

Ø

Ø

Ø

Ø

Ø

Ø

until fast

until fast

until fast

until fast

until fast

until fast

until fast

blink stops

blink stops

blink stops

blink stops

blink stops

blink stops

blink stops

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

TO VIE W AND CHANGE TH

E SET POINTS

AND DEL AY TIMES

 c ycles through the choices. The LED f or each choice
 will turn ON.

To change a setting, use

Press ENTER until quick blinking s tops to store your new
choice.

After 5 seconds if y ou havenít pressed any buttons,
control will return to normal oper ation.

Start-up Timer
The Start-up Timer bypases the Contr ol during motor
start-up to avoid false trips because of curr ent inrush. For
convenience, the TIMING BEGINS WHEN THE MO

TO R

STARTS. The S tart-up LED stays lit until the start-up period
is over.

The start-up time should be:

ï

Long enough so that the load has s tabilized.

To bypass Start-up Timer set time to zer o seconds.

Dela y Timer (Max Set P oint)
To avoid nuisance trips fr om short overloads, Dela y
Timers bypass the Contr ol for the select ed time. The
relays wonít trip until the time is exceeded. If t he trip
condition goes away before the time is up, the timer
resets to zer o.

ï

Start with minimum Dela y. If y ou are getting trips
where you donít w ant them, increase the Dela y
Time.

Adjusting R ate Set P oint
The Rate Set P oint limits sudden load changes.

1 = Fastest (most sensitive)
40 = Slo west (least sensitive)

Start at about 15. Go slo wer if y ou get nuisance trips. Go
faster for more sensitivity.

888-600-3247

10 PICKER ROAD

508-347-2606

STURBRIDGE, MA 01566

FAX  508-347-2064

11/2001

53 TECHN OLOGY PARK ROAD
STURBRIDGE, M A 01566

888-600-3247
508-347-2606
FAX 508-347-2064

•   After hook-up, find your HP, KW or % from the chart

•   Decide if you want to display HP, % or KW

shown

press

FRONT PANEL SET-UP TIPS

None of the settings will be changed until you hold

Five seconds after you have pressed a button, the 

Control will return to normal operation.

(or if you change the hook-up).

TO VIEW AND CHANGE THE SET POINTS

AND DELAY TIMES

cycles through the choices. The LED for each choice

Press ENTER until quick blinking stops to store your new 

choice.

After 5 seconds if you haven’t pressed any buttons, 

control will return to normal operation.

Start-up Timer

The Start-up Timer bypasses the Control during motor 

start-up to avoid false trips because of current inrush. For 

convenience, the TIMING BEGINS WHEN THE MOTOR 

STARTS. The Start-up LED stays lit until the start-up 

period is over.

The start-up time should be:

•   Long enough so that the load has stabilized

To bypass Start-up Timer set time to zero seconds

Delay Timers (Max Set Point)

To avoid nuisance trips from short overloads, Delay 

Timers bypass the Control for the selected time. The 

relays won’t trip until the time is exceeded. If the trip 

condition goes away before the time is up, the timer 

resets to zero.

•  Start with minimum Delay. If you are getting 

trips where you don’t want them, increase the Delay 

Time.

Adjusting Rate Set Point
The Rate Set Point limits sudden load changes
 1  = Fastest (most sensitive)
40 = Slowest (least sensitive)

Start at about 15. Go ‘slower’ if you get nuisance trips. Go 
‘faster’ for more sensitivity.

will turn ON.

10/2015

Содержание ROC-50

Страница 1: ...ity it can be used Otherwise install a separate transformer It is okay if the secondary is grounded BE SURE TO NOTE WHICH TWO PHASES SUPPL YTHE TRANSFORMER In 120 208V three phase system the 120V MUST come from a transformer connected to two of the phases The 120V phase to ground voltage cannot be used CURRENT The current signal is taken from the REMAINING phase This current sample passes through ...

Страница 2: ...0 55 0 183 6 ON 1 40 55 0 138 6 ON 1 50 55 0 110 6 ON 1 60 84 0 140 1 ON 1 100 5 75 84 0 112 1 ON 1 100 5 100 130 130 1 ON 1 150 5 125 130 104 1 ON 1 150 5 150 173 115 1 ON 1 200 5 200 216 108 1 ON 1 250 5 250 260 104 1 ON 1 300 5 300 346 115 1 ON 1 400 5 MUL TIPLIERS For nominal voltages other than 460 volts multiply 460V full scale by 208V 45 230V 5 380V 83 415V 9 575V 1 25 For Kilowatts multipl...

Страница 3: ...nt Gold flashed contacts Reed Relays Mercury Switches 4 20 MILLIAMP ANAL OG OUTPUT The Analog Output is directly proportional to Full Scale capacity It is always active 500 ohm maximum con nected impedance Terminal 2 4 20mA Positive Terminal 3 4 20mA Negative Use twisted pair or in noisy environments use shielded cable Ground shield at other end Use the Full Scale capacity from the chart to scale ...

Страница 4: ...rip until the time is exceeded If t he trip condition goes away before the time is up the timer resets to zero ï Start with minimum Dela y If you are getting trips where you donít want them increase the Delay Time Adjusting R ate Set P oint The Rate Set Point limits sudden load changes 1 Fastest most sensitive 40 Slo west least sensitive Start at about 15 Go slo wer if you get nuisance trips Go fa...

Отзывы: