FOR MOTORS LESS THAN 5 HP

Take more “turns” of the leg through the Toroid. Each
time the wire passes through the Toroid is a “turn”.

This is one turn.                       

 This is two turns.

FOR MOTORS GREATER THAN 50 HP

A Current Transformer is used to reduce the primary
current. The 5-amp secondary passes through the Toroid.

Pass secondary of CT through toroid.

CAUTION

When current is flowing through the primary of the
external current transformer, always have a wire be-
tween the two brass Terminals on the CT.

If they are left open, dangerous and destructive volt-
ages can develop.

RANGE FINDER TOROID

HOOKING UP THE RESET

Control can be reset three ways:

• Manually with the Reset button on the control.
• Remotely with a remotely located reset button

or relay.

• Automatic with a jumper.

Remote Reset-

Momentarily connect Terminal 4 to Terminal 6 for max.
Momentarily connect Terminal 5 to Terminal 6 for rate.

Automatic Reset-

Jumper Terminal 4 or 5 to Terminal 6.

The terminals for Reset generate a small amount of
current (8-12 milliamps). To reset, you just need to
connect the terminal to the circuit common (Terminal 6).

The switches or relays that you use must be suitable for
low current (Gold flashed contacts, Reed Relays, Mercury
Switches).

4-20 MILLIAMP ANALOG OUTPUT

The Analog O utput is directly proportional to Full Scale
capacity. It is always active. 500 ohm maximum con-
nected impedance.

Terminal 2

4-20mA

Positive

Terminal 3

4-20mA

Negative

Use twisted pair or in noisy environments, use shielded
cable. Ground shield at other end.

Use the Full Scale capacity from the chart to scale
external meter, chart recorders or computers.

THE ROC-50 POWERS THE 4-20MA SIGNAL.

DON’T USE AN EXTERNAL DC POWER SUPPLY.

SPECIFICATIONS ROC-50

ENCLOSURE

Glass-filled Polycarbonate

NEMA 4, 4X - STYLE

(3 1/ 4” x 6 1/ 4” x 2”)
(83 mm x 160 mm x 54 mm)

CAPACITY

To 50 horsepower directly

through Toroid

To 500 horsepower with external

Current Transformer & Toroid

DIGITAL LOAD DISPLAY

.4” LED 3 Digit

RELAY OUTPUTS

(2) Form C 3 AMP @ 300 VAC or

1/ 8 HP @ 240 VAC

Latch when tripped

1 1/ 8” Hole

3 1/ 2”

2”

2 3/

8”

ANALOG OUTPUT

4-20mA; powered by the

RO C-50 500 O HM

maximum connected

impedance

RESPONSE TIME

25 Milliseconds

TEMPERATURE

0ºC - 55ºC

TIMERS

Start-up and Trip Delay(s)

0-90 second

0-2 second in .1 second

increments

2-90 second in 1 second

increments

RANGE FINDER TOROID

HOOKING UP THE RESET

FOR MOTORS LESS THAN 5 

HP

FOR MOTORS GREATER THAN 50 

HP

4-20 MILLIAMP ANALOG OUTPUT

THE R

OC

-50 POWERS THE 4-20 MA SIGNAL

DON’T USE AN EXTERNAL DC POWER SUPPLY!

SPECIFICATIONS ROC-50

CAUTION

Содержание ROC-50

Страница 1: ...ity it can be used Otherwise install a separate transformer It is okay if the secondary is grounded BE SURE TO NOTE WHICH TWO PHASES SUPPL YTHE TRANSFORMER In 120 208V three phase system the 120V MUST come from a transformer connected to two of the phases The 120V phase to ground voltage cannot be used CURRENT The current signal is taken from the REMAINING phase This current sample passes through ...

Страница 2: ...0 55 0 183 6 ON 1 40 55 0 138 6 ON 1 50 55 0 110 6 ON 1 60 84 0 140 1 ON 1 100 5 75 84 0 112 1 ON 1 100 5 100 130 130 1 ON 1 150 5 125 130 104 1 ON 1 150 5 150 173 115 1 ON 1 200 5 200 216 108 1 ON 1 250 5 250 260 104 1 ON 1 300 5 300 346 115 1 ON 1 400 5 MUL TIPLIERS For nominal voltages other than 460 volts multiply 460V full scale by 208V 45 230V 5 380V 83 415V 9 575V 1 25 For Kilowatts multipl...

Страница 3: ...nt Gold flashed contacts Reed Relays Mercury Switches 4 20 MILLIAMP ANAL OG OUTPUT The Analog Output is directly proportional to Full Scale capacity It is always active 500 ohm maximum con nected impedance Terminal 2 4 20mA Positive Terminal 3 4 20mA Negative Use twisted pair or in noisy environments use shielded cable Ground shield at other end Use the Full Scale capacity from the chart to scale ...

Страница 4: ...rip until the time is exceeded If t he trip condition goes away before the time is up the timer resets to zero ï Start with minimum Dela y If you are getting trips where you donít want them increase the Delay Time Adjusting R ate Set P oint The Rate Set Point limits sudden load changes 1 Fastest most sensitive 40 Slo west least sensitive Start at about 15 Go slo wer if you get nuisance trips Go fa...

Отзывы: