7.5.5 System ID setting
In order for the a correct operation of the system, a unique number (ID) must be assigned to each generator.
To do this, proceed as follows:
Screen
Procedure
Manually set the unit ID for each Generator (every Generator must have a consecutive
number). To set the ID see 8.2.2 and relatives
(Identifier parameter)
Hold pressed the button on the BOX controller for more than 10 seconds to start the
searching procedure for the generators connected to it. The parallel box scans every
connected generator and recognise their ID previously setted.
7.5.6 System status
The following functions are available on all of the connected generators:
•
start/stop production
•
open or close the outlet valve
•
set working pressure
•
monitor the status of each generator connected to the system
To access the status screen, simply scroll the touch screen from right to left or vice-versa.
The following data are displayed for each of the generators:
Master
Generator that reads and controls line pressure (Master flow controller)
Slave
Generator connected to the system as slave
Out line
Generator offline: communication with controller interrupted
Alarm
Generator alarm
Pre-Alarm
Generator pre-alarm
NOTE
: the slave generators may display different pressures; if this difference is less than 1 bar, the situation
is normal.
7.5.7 Master flow controller
Normally, the system chooses the generator with ID 1 as the "master flow controller", that is the appliance
designated to read and control line pressure.
To force the system to use a different generator, press the touch screen for half a second to display the
status screen.
Press the touch screen for half a second
To confirm, press the touch screen for half a second again
Operating manual NG(A) CASTORE XS iQ
24