background image

Replaces same of Rev. C 7/97

1780.D 7/00

Instruction

Instruction

Instruction

Instruction

Instruction

     

Manual

Manual

Manual

Manual

Manual

Liquitron™ DC4500 Series

For file reference, please record the following data:

Model No: 
Serial No: 
Installation Date: 
Installation Location: 

When ordering replacement parts for your LMI Controller or accessory, please include
the complete Model Number and Serial Number of your unit.

[email protected]

www.novatech-usa.com

Tel: (866) 433-6682 

Fax: (866) 433-6684

Tel: (281) 359-8538 

Fax: (281) 359-0084

Содержание Liquitron DC4500 Series

Страница 1: ...r file reference please record the following data Model No Serial No Installation Date Installation Location When ordering replacement parts for your LMI Controller or accessory please include the com...

Страница 2: ...20 3 8 Clock 21 3 9 View Biocide 22 3 10 Add Biocide 23 3 11 Biocide Lockout 24 3 12 Biocide Prebleed 25 3 13 Manual Outputs 26 3 14 Advanced Setup 27 3 15 Temperature 28 3 16 H2 O Meter 29 4 0 Start...

Страница 3: ...LEEDS lockout timer limits maximum FEED time FEED time calculated as a percentage of total BLEED time FEED based on a timed cycle pump is on for a percentage of this timed cycle FEED based on flow met...

Страница 4: ...LAY DISPLAY DISPLAY DISPLAY FLOW FLOW FLOW FLOW FLOW indicator lights when there is a loss of system flow Operates only if flow switch is installed BLEED BLEED BLEED BLEED BLEED indicator lights when...

Страница 5: ...PE enclosure When ordered 115 VAC units come fully wired to include input power cord and relay output pigtails to allow for simple installation The unit can be hardwired through conduit to the lower j...

Страница 6: ...sions When using the prewired unit the enclosure is configured as NEMA 12X If the unit is connected through watertight conduit the enclosure is configured as NEMA 4X The following clearances should be...

Страница 7: ...rd and four 4 12 inch output pigtails for plug in connec tion of controlled devices A four pin connector is provided for the conductivity probe and temperature compensation probe The DC4500 controller...

Страница 8: ...2 1 Neutral TB1 4 Ground TB4 4 Bleed Blowdown Control Relay Output Bleed Blowdown Control Relay Output Bleed Blowdown Control Relay Output Bleed Blowdown Control Relay Output Bleed Blowdown Control Re...

Страница 9: ...put Flowmeter Input Flowmeter Input The inputs are reversible when the flowmeter connection is a relay and has no polarity TB10 1 TB10 2 Flow Switch Input Flow Switch Input Flow Switch Input Flow Swit...

Страница 10: ...les that may cause electrical interference Signal Output TB11 1 Signal Return TB11 2 Conductivity Probe Hardwire Only Conductivity Probe Hardwire Only Conductivity Probe Hardwire Only Conductivity Pro...

Страница 11: ...gure 5 Bottom of controller with cover open Figure 5 Bottom of controller with cover open Figure 5 Bottom of controller with cover open Figure 5 Bottom of controller with cover open 866 433 6682 281 3...

Страница 12: ...4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 TB4 TB5 TB6 TB2 TB1 TB3 TB7 TB8 TB9 TB11 TBIO FUSE DC4500 TEST SWITCH AC POWER LINE N O LINE N C NEUTRAL SOLENOID VAL...

Страница 13: ...4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 TB4 TB5 TB6 TB2 TB1 TB3 TB7 TB8 TB9 TB11 TBIO FUSE DC4500 ALARM INPUT POWER MAIN AC POWER VIO ORG GREY RED AC POWER LINE N O LINE N C NEUTRAL...

Страница 14: ...in the test mode After reviewing or changing the conductivity controller programming setpoints the unit must be returned to the System Run or conductivity reading screen to allow automatic control to...

Страница 15: ...w to another line item When not in the System Run mode the outputs to the control relays are disabled The following is the order of items in the main menu CONDUCTIVITY SET POINT DIFFERENTIAL LOW ALARM...

Страница 16: ...3400 S 3400 S 3400 S 3400 S 3400 CAL CAL CAL CAL CAL S 1700 S 1700 S 1700 S 1700 S 1700 CALIBRATION LIMIT CALIBRATION LIMIT CALIBRATION LIMIT CALIBRATION LIMIT CALIBRATION LIMIT CONDUCTIVITY SET POIN...

Страница 17: ...nd allows the value to be changed The value will have a flashing cursor indicating that it can be changed Press the UP or DOWN key to increase or decrease the value Press ENTER to save the value SET P...

Страница 18: ...s screen to change the value The value will have a flashing cursor indicating that it can be changed Press the UP or DOWN key to increase or decrease the value Press ENTER to save the DIFFERENTIAL val...

Страница 19: ...o save the value CONDUCTIVITY SET POINT LOW ALARM HIGH ALARM FEED CLOCK VIEW BIOCIDE ADD BIOCIDE LOCKOUT PREBLEED MANUAL OUTPUT ADVANCED SETUP TEMPERATURE H2 O METER DIFFERENTIAL LO ALARM LO ALARM LO...

Страница 20: ...e the value CONDUCTIVITY SET POINT LOW ALARM HIGH ALARM FEED CLOCK VIEW BIOCIDE ADD BIOCIDE LOCKOUT PREBLEED MANUAL OUTPUT ADVANCED SETUP TEMPERATURE H2 O METER DIFFERENTIAL HI ALARM HI ALARM HI ALARM...

Страница 21: ...above Use the UP or DOWN key to change the settings and press ENTER to save that setting CONDUCTIVITY SET POINT LOW ALARM HIGH ALARM FEED CLOCK VIEW BIOCIDE ADD BIOCIDE LOCKOUT PREBLEED MANUAL OUTPUT...

Страница 22: ...ck is currently running in Again press the UP or DOWN key to change the value and ENTER to save The next screen displayed is the DAY screen Pressing the UP or DOWN key changes the setting and pressing...

Страница 23: ...pump will run for 55 minutes Based on the above example biocide pump 1 is programmed to turn on at 3 00 pm for 55 minutes during week 4 on Monday VIEW BIOCIDE VIEW BIOCIDE VIEW BIOCIDE VIEW BIOCIDE V...

Страница 24: ...CIDE LOCKOUT PREBLEED MANUAL OUTPUT ADVANCED SETUP TEMPERATURE H2 O METER DIFFERENTIAL BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCIDE ADD BIOCI...

Страница 25: ...T BIOS LOCKOUT BIOS LOCKOUT BIOS LOCKOUT BIOS LOCK 1 45 BIOS LOCK 1 45 BIOS LOCK 1 45 BIOS LOCK 1 45 BIOS LOCK 1 45 BIOS LOCK 2 12 BIOS LOCK 2 12 BIOS LOCK 2 12 BIOS LOCK 2 12 BIOS LOCK 2 12 Bleed wil...

Страница 26: ...PREBLEED BIOS PREBLEED BIOS PREBLEED BIOS PREBLEED Biocide Prebleed Screen Biocide Prebleed Screen Biocide Prebleed Screen Biocide Prebleed Screen Biocide Prebleed Screen BIOS PREBLEED BIOS PREBLEED...

Страница 27: ...s the MANUAL OUTPUT sub menu screens MANUAL OUTPUT MANUAL OUTPUT MANUAL OUTPUT MANUAL OUTPUT MANUAL OUTPUT ADD BIOCIDE CONDUCTIVITY SET POINT LOW ALARM HIGH ALARM FEED CLOCK VIEW BIOCIDE LOCKOUT PREBL...

Страница 28: ...DEFAULTS ADD BIOCIDE CONDUCTIVITY SET POINT LOW ALARM HIGH ALARM FEED CLOCK VIEW BIOCIDE LOCKOUT PREBLEED MANUAL OUTPUT ADVANCED SETUP TEMPERATURE H2 O METER DIFFERENTIAL ADVANCED SETUP ADVANCED SETU...

Страница 29: ...screen accesses this option change Pressing the UP or DOWN key toggles between displaying F or C Pressing ENTER a second time saves the displayed Tempera ture selection TEMP F 032 TEMP F 032 TEMP F 0...

Страница 30: ...AL TOTAL 00000 GAL TOTAL 00000 GAL TOTAL 00000 GAL TOTAL 00000 GAL TOTAL 00000 GAL Use or key Use or key Use or key Use or key Use or key to to to to to select RATIO or RESET select RATIO or RESET sel...

Страница 31: ...nd that the probe is fully emersed This prevents the electrode from becoming air bound System shut off isolation valves are recommended for installation on either side of the conductivity sensing elec...

Страница 32: ...rcent of the total bleed blowdown time 4 LIMIT Chemical inhibitor feed at the same time as system bleed or blowdown The Feed pump can be controlled by either a powered relay output or by direct variab...

Страница 33: ...eed Control mode supplies a low voltage signal to the pump for pump stroke rate control The terminal connections on the I O pc board for these modes are shown ON OFF ON OFF ON OFF ON OFF ON OFF VARIAB...

Страница 34: ...Option Trip Actuation 4 20 mAmp settings Display Mode Pulse Output Pump Control and ControlCoolingTower Go to the CLOCK menu screen see CLOCK programming sheet in manual and enter the current day and...

Страница 35: ...s conductivity is brought back to the desired setpoint This is done when the probe is installed on the drain line itself It allows for minimal piping installa tion The programmed settings for this met...

Страница 36: ...board test switch to aid in troubleshooting the unit and system The switch is located under the access cover on the lower section of the controller see Figure 5 The conductivity test switch allows the...

Страница 37: ...own in Figure 7 The probe should be cleaned parallel to the carbon electrodes NOT perpen dicular Frequency The probe should periodically be cleaned to maintain accurate measurements The frequency of c...

Страница 38: ...ct wiring to valve Check wiring by using Relay Test program Valve has failed Test per manufacturers instructions Incorrect Blowdown setpoint Verify setpoint and rising falling trip selection Low Condu...

Страница 39: ...Bleed 10 Feed after Bleed Limit 10 minutes Limit Feed Bleed 10 minute limit Flow Alarm On Off Off Trip Rise Fall Rise 4 mAmp setting 0 S 20 mAmp setting 20 000 S Display uS PPM TDS S Pump Pulse Feed...

Страница 40: ...0 C to 100 C Temperature resolution 1 8 F 1 C Probe Input Probe Input Probe Input Probe Input Probe Input Cell constant of 1 5 ESD Protection 700 Volts Three 3 sample readings second display updated e...

Страница 41: ...42 10 0 Product Exploded View 866 433 6682 281 359 8538 sales novatech usa com www novatech usa com...

Страница 42: ...C4500 terminal cover 12 34074 Gasket foam 13 34088 Cover utility box 14 32094 Label 15 35378 Label DC4500 16 36526 Front panel assembly 17 31617 Cover Liquitron 18 30588 Label 19 32211 Cap 0 125 x 0 3...

Страница 43: ...MI Milton Roy All Rights Reserved Printed in USA Specifications subject to change without notice sales novatech usa com www novatech usa com Tel 866 433 6682 Fax 866 433 6684 Tel 281 359 8538 Fax 281...

Отзывы: