PROFIBUS SOFTWARE DEFINITION
53
Digital Output 1
Config
Enumeration with a range 0-8. The
enumeration is as follows:
0: Digital Output = Disabled
1: Digital Output = StrokePulse
2: Digital Output = PumpRunning
3: Digital Output = PumpStandby
4: Digital Output = AlarmOut
5: Digital Output = INTEXTMode
6: Digital Output = UserAlarmOut
7: Digital Output = PumpStopped
8: Digital Output = TimedEvent
Input/Output UINT8
54
Digital Output 1
State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output BOOL
55
Digital Output 2
Config
Enumeration with a range 0-8. The
enumeration is as follows:
0: Digital Output = Disabled
1: Digital Output = StrokePulse
2: Digital Output = PumpRunning
3: Digital Output = PumpStandby
4: Digital Output = AlarmOut
5: Digital Output = INTEXTMode
6: Digital Output = UserAlarmOut
7: Digital Output = PumpStopped
8: Digital Output = TimedEvent
Input/Output UINT8
56
Digital Output 2
State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output BOOL
57
Analog Output
Config
Enumeration with a range 0-2. The
enumeration is as follows:
0: Analog Output = Disabled
1: Analog Output = Flow
2: Analog Output = MirrorInput
Input/Output UINT8
4.1.5 Modules 58-64: System Settings
Module Name
Description
Direction
Data
Type
58
Remote Internal
Mode
Enumeration
0 = Manual
1 = Cycle Timer
2=Weekly Timer
Input/Output UINT8
59
Remote External
Mode
Enumeration
0= mA
1= Pulse
2 = Batch
Input/Output UINT8
60 Lock Style
Enumeration
1=No_Lock
2=All_Lock, 3=All_Lock_Power_Unlock,
4=All_Lock_Password,
5=All_Lock_Power_Password).
Input/Output UINT8
61 Password
Integer with a range of 0000-9999.
Input/Output UINT8